58
negative temperature chilling
(temperature detected by the
needle probe)
r5
1 600 Min. 90 maximum time for positive
temperature controlled blast
chilling
r6
1 600 Min. 240 maximum time for negative
temperature controlled blast
chilling
r7
-99.0 -99.0 °C/°F(1) 0.0 working setpoint during
positive temperature blast
chilling (chiller compartment
temperature)
r8
-99.0 -99.0 °C/°F(1) -40 working setpoint during
negative temperature blast
chilling (chiller compartment
temperature)
r9
-99.0 -99.0 °C/°F(1) 2.0 working setpoint during storage
after positive temperature blast
chilling (chiller compartment
temperature)
rA
-99.0 -99.0 °C/°F(1) -20.0 working setpoint during storage
after negative temperature blast
chilling (chiller compartment
temperature)
9.2 Second level configuration parameters
PARAM MIN. MAX. U.M. DEF. TEMPERATURE READING
INPUTS
CA1 -25.0 25.0 °C/°F(1
)
0.0 offset chiller compartment
probe
CA2 -25.0 25.0 °C/°F(1
)
0.0 offset needle probe
P0
0 1 --- 0 type of probe
0 = PTC
1 = NTC
P1
0 1 --- 1 decimal point degree Celsius
(for the reading displayed
during normal functioning)
1 = yes