H Handover to the user
When handing over the air conditioning system,
explain the operation and operating conditions to the
user.
Explain operation – with particular emphasis on all
safety-related actions.
Highlight the following points in particular:
Point out that modifications or repairs may be
carried out only by an approved contractor.
To ensure safe and environmentally compatible
operation, an annual inspection, and also
cleaning and maintenance if required, must be
carried out.
Point out the possible consequences (personal
injury and possible danger to life or material
damage) of not carrying out inspection, cleaning
and maintenance correctly, or omitting it
altogether.
Hand over the installation and operating
instructions to the user for safekeeping.
1.3 Notices regarding these instructions
The figures are shown together at the end of these instructions. The text
contains references to the figures.
Depending on the model, the products may be different to those shown
in these instructions.
2Product Information
2.1 Scope of delivery
Key to Fig. 1:
[1] Outdoor unit (filled with refrigerant)
[2] Indoor unit (filled with nitrogen)
[3] Cold catalyst filter
[4] Drainage elbow with gasket
(for outdoor unit with floor or wall mounting bracket)
[5] Remote control with batteries
[6] Remote control holder with fixing screw
[7] Fixing materials (5 screws and 5 wall plugs)
[8] Set of printed documents for product documentation
[9] 4 anti-vibration couplings for the outdoor unit
2.2 Product dimensions and minimum clearances
2.2.1 Indoor unit and outdoor unit
Figures 2 to 4.
2.2.2 Refrigerant pipes
Key to Fig. 5:
[1] Gas-side pipe
[2] Liquid-side pipe
[3] Siphon-shaped elbow as oil separator
If the outdoor unit is positioned higher than the indoor unit, install a
siphon-shaped elbow on the gas side after no more than 6 m and every
6 m thereafter ( Fig. 5, [1]).
Observe maximum pipe length and maximum difference in height
between indoor unit and outdoor unit.
Table 2 Pipe length and difference in height
Table 3 Pipe diameter depending on appliance type
Table 4 Alternative pipe diameter
Table 5
Maximum pipe
length
1)
[m]
1) Gas side or liquid side
Maximum difference
in height
2)
[m]
2) Measured from bottom edge to bottom edge.
CLL2000 23 20 8
CLL2000 26 20 8
CLL2000 35 20 8
CLL2000 53 25 10
CLL2000 70 25 10
Pipe size
Unit type Liquid side [mm] Gas side [mm]
CLL2000 23 6,35 (1/4") 9,53 (3/8")
CLL2000 26 6.35 (1/4") 9.53 (3/8")
CLL2000 35 6.35 (1/4") 9.53 (3/8")
CLL2000 53 6.35 (1/4") 12.7 (1/2")
CLL2000 70 9.53 (3/8") 15.9 (5/8")
Pipe diameter [mm] Alternative pipe diameter [mm]
6.35 (1/4") 6
9.53 (3/8") 10
12.7 (1/2") 12
15.9 (5/8") 16
Specification of the pipes
Min. piping length 3 m
Additional refrigerant if the pipe length
exceeds 5 m (liquid side)
With Ø 6.35 mm (1/4"):
15 g/m
With Ø 9.53 mm (3/8"):
30 g/m
Pipe thickness with 6.35 mm to 12.7 mm
pipe diameter
≥0.8mm
Pipe thickness with 15.9 mm pipe
diameter
≥1.0mm
Thickness of heat insulation 6 mm
Material of heat insulation Polyethylene foam