General Informations
The device can be used in electrical panels, laboratories and test devices. With
the assistance of a current transformer, it measures the AC current passing
through the system in terms of Amper unite. After energizing the device,
“dA -A “ message appears on it's screen for 2 seconds and then it starts to
show the current value
■ The current transformer ratio can be adjusted between 5/5 and 10000/5 using
the touch buttons on the front panel of the device.
■ Stores the maximum demand value and the peak value on its memory and
keeps these values even if the energy supply goes off.
■ When the measured value of the seconder current reaches 5,1 A, “ OvEr”
message starts to flash on the screen to warn the user that the value of the
current exceeded the limit values.
Button Functions:
Using the direction buttons, it is possible to go through the nemu up and down.
“SEt” message will appear on the screen if the set button pressed. To set one
of the parameters set button must be pressed again inorder to enter that menu.
The first parameter that can be set in the set menu is transformer's primer
current value, that would flash on the screen with the message “ CtrF” while
setting. Pressing the set button and the direction buttons can increase and
decrease this value “ between 5 and 10000”. after reaching the required value
set button should be pressed to store this value on the device. After that
pressing the down button leads to the demand time setting with dd-t flashing on
the screen.
To make an adjustment, set button must be pushed. With the direction buttons
the value can be adjusted “between 10 and 60 minutes”. After reaching the
required value pressing set button would store this value. Next what would
appear in the SEt menu pressing the down direction button is qUit. Pressing the
set button would exit the set menu.
The next menu after set menu is Clr, “ can be reached by pressing down button”.
To clear the maximum demand and the peak value set button must be pressed.
After the Clr menu qUit show appear. Pressing set there would return the
screen to the measurement screen.
While in measurement screen, pressing the up direction button shows the
maximum peak current value occurred since the last operation done, pressing
the down direction button shows the maximum demand occurred since last Clr
operation done.
Technical Data
Operational Voltage (Un) : 230Vac
Operating range : (0,8-1,1) x Un
Frequency : 50/60 Hz
Power Consumption : < 4VA
Measurement Sensitivity : %1 +1 digit
Current Transformer
Ratio : 5/5..........10000/5 A
Display : 4 Digits Led Display
Protection Class : IP 20
Terminal Protection Class : IP 00
Operation Temperature : - 5 °C .... + 50 °C
Operation Humidity : %15 ...... %95
(without consensation)
Installation : to the panel tap
Dimensions :DAM – A – 96 ( 96x96x80 mm)
: DAM – A – 72 ( 72x72x80 mm)
: DAM – A – 48 ( 48x48x50 mm)
Current direction
L1
N
X/5 A
Warning !!!
- The message Err1 or Err2 on the screen means that the
device has got a failure
- Can not be used without current transformer, a current
that is higher that 5 A passing through the measurement
inputs may damage the device.
- To clean the device use dry dust cloth after de-energizing
the device
SET
SET
SET
SET
Exit
SET
L1
N
Auxiliary supply
230 Vac,50-60 Hz
k1
l1
Current Transformer
inputs (X / 5 A)
Connection Scheme:
Entrance to the
parameters
Current transformer
value
Demand
time
Clears the
demand
and peak
values
DAM – A
®
SET
Increase
Decrease
SET
Increase
Decrease
DIGITAL UNIVERSAL AMPERMETER (True RMS)
► With Demand