Iek ARMAT R10N 2P 40А 300мА тип AC AR-R10N-2-040C300 Инструкция к товару онлайн [2/2] 858350

Iek ARMAT R10N 2P 80А 30мА тип AC AR-R10N-2-080C030 Инструкция к товару онлайн [2/2] 858360
ARMAT
2
3
4
5 6 7
Residual current operated circuit-breaker without integral overcurrent
protection R10N of ARMAT series of IEK trademark (hereinafter referred to as –
RCCB) designed for operation in single-phase or three-phase AC electrical
networks with a voltage of up to 400 V and a frequency of 50/60 Hz and meets the
requirements LVD Directive No. 2014/35/EU, EMC Directive No. 2014/30/EU and
RoHS 2011/65/EU.
ÀRÌÀÒ – series;
R – (RCÑÂ) – VDT;
N – standard size (width is a multiple of 18 mm);
ARMAT RCCB R10N Õ Õ Õ , type Õ IEK
1 2 3 4 5
Õ – quantity of poles: 2Ð – two poles; 4Ð – four poles;
1
Basic information about product
RCCBs are not designed to trip the short-circuit currents and overload
currents.
Type designation
10 – rated conditional short-circuit current – 10 kÀ;
IEK – trademark.
Õ – RCCB type according to the operating conditions in the presence of a DC
4
component: ÀÑ; À;
Õ – selective execution S (for nonselective RCCB not pointed);
5
Õ – designation of rated residual breaking current: 10 mÀ; 30 mÀ;
3
100 mÀ; 300 mÀ;
Õ – rated current designation: 25 À; 32 À; 40 À; 50 À; 63 À; 80 À; 100 À;
2
An example of a recording of a selective two-pole residual current circuit-
breaker for a rated current of 80 A with a rated residual breaking current of 300 mA,
with the type of operating characteristic according to AC type differential current:
ARMAT RCCB R10N 2P 80 A 300 mÀ AC-S type IEK
RESIDUAL CURRENT OPERATED
CIRCUIT-DREAKER WITHOUT INTEGRAL
OVERCURRENT PROTECTION
RCCB R10N OF ARMAT SERIES
Operation manual
2
3
4
5 6 7 8
Specifications and operating conditions
An example of a recording of a selective two-pole residual current circuit-
breaker for a rated current of 63 À with a rated residual breaking current of 300 mA,
with the type of operating characteristic according to À type differential current:
ARMAT RCCB R10N 2P 63 A 300 mÀ A-S type IEK
Parameter denomination
Value for circuit-breakers of type
R10N of AC type
R10N of A type
Pole number
2, 4
Rated operation voltage U, V
i
2 poles
230
4 poles
400
Rated mains frequency, Hz
50/60
Rated insulation voltage, V
415
Rated impulse withstand voltage, V
4000
Rated current I , À
n
common
25, 32, 40, 50, 63, 80, 100
S type
63, 80, 100
Rated residual breaking
current (setting) I , mÀ
Δn
common
10, 30, 100, 300
S type
100, 300
Rated residual non-breaking current I , mÀ
Δn0
0,5 I
Δn
Rated making and breaking capacity I , À
m
10 In or 500
(the larger value is selected)
Rated residual making and breaking capacity I , À
Δm
10 In or 500
(the larger value is selected)
Rated conditional short-circuit current, I , kA
nc
10
Rated conditional residual short-circuit current, I , kA
Δc
10
Operating curve type according to operation with presence
of DC component
ÀÑ
À
Mechanical wear-resistance, ON-ÎFF cycles
і10 000
Commutation wear resistance, ON-ÎFF cycles
і 6 000
2
Cross-section of connected conductors, mm
1,5–35
Âîçìîæíîñòü ïîäêëþ÷åíèÿ øèí ê
ïîëþñàì
N, 3 or N, 3, 5, 7
PIN
up to 63 À inclusive
PIN; FORK
80 À and 100 À
PIN
Screw tightening torque, N·m
recommended
2,5
max
5
Degree of protection IEC 60529
IP20
Base altitude, m
Ј 2000
Óãîë çàäåðæêè òîêà a
Tripping current
Lower limit
Upper limit
0°
0,35 I
Dn
1,4 I or 2 I *
Dn Dn
90°
0,2 I
Dn
135°
0,11 I
Dn
Tripping current range for RCCB of À type
* For tests according to 9.2.1.1 IEC 61008 with factor 1,4 for RCCBs with I > 0,01 À
Dn
and with factor 2 for RCCBs with I < 0,01 À.
Dn
Type
I
n
I
Dn
Maximum value of breaking time for RCCB of À type in the case of half-wave impulse
residual current (root mean square) À, s
1,4I
Dn
2I
Dn
2,8 I
Dn
4I
Dn
7I
Dn
0,35 À
0,5 A
350 A
Common
Any value
< 0,030
0,3
0,15
0,04
0,04
0,030
0,3
0,15
0,04
0,04
> 0,030
0,3
0,15
0,04
0,04
S
Àbove 25
Àbove 0,030
0,5
0,2
0,15
0,15
RCCB type
À, mm
Â, mm
Ñ, mm
L, mm
Weight, kg
Two poles for currents Ј 63 À
84,6
81,5
23,0
36,0
0,20
Four poles for currents Ј 63 À
72,0
0,21
Two poles for currents of 80 A and 100 A
87,6
84,0
25,5
36,0
0,33
Four poles for currents of 80 A and 100 A
72,0
0,45
Dimensions – maximum
Limit values of breaking and non-breaking time for AC residual current (root mean square)
for RCCBs of ÀÑ and À types
Type
I
n
I
Dn
Standard values of breaking and non-breaking time, s, at
the residual current
Note
I
Dn
2I
Dn
5I
Dn
500 À
Common
Any value
Any value
0,30
0,15
0,04
0,04
Maximum breaking
time
S
Above 25
Above 0,030
0,5
0,2
0,15
0,15
0,13
0,06
0,05
0,04
Minimum
non-breaking time
Maximum value of breaking time for half-wave impulse residual current (root mean square)
for RCCB of À type
Overall and mounting dimensions and RCCB weight
Electric schematic diagrams of RCCB
L
71
45
B
A
C
35,5
62
43,7 5,5
Delivery set consists of:
RCCBs have an indicator of the switching position of the contacts and an
indicator of actuation from the residual current. Colored indicators are used as
pointers. The switching position of the RCCB is indicated by the color state of the
contact position indicator:
Completeness of set
RCCB — 1 pc;
– îperation manual — 1 copy.
Safety requirements
off-position – green indicator;
on-position – red indicator.
An additional yellow indicator indicates actuation from residual current.
The minimum distances from the RCCB to the metal parts of the switchgear
products should correspond to IEC 61008-1.
RCCBs are installed in series with a circuit breaker or fuse for protection
against overload currents and short-circuit currents. The rated current of the RCCB
should be selected in one step higher than the rated current of the circuit breaker
or fuse in front of it to ensure that the RCCB can conduct the temporary overcurrents.
To operate RCCB without a serial protection device (circuit breaker or fuse)
in the electric installation circuit.
IT IS RECOMMENDED
IT IS FORBIDDEN
à) cock the RCCB by means of the control handle. If the RCCB is cocked, it
means that there was a current leakage to earth in the electrical installation, caused
by an unstable or short-term insulation fault. Check the RCCB operability by
pressing the "TEST" button;
If after switching on of the RCCB immediately or after a while it turns off, it is
necessary to determine the type of malfunction in the electrical installation in the
following order:
Immediate operation of the RCCB (disconnection of the circuit protected by
the device and yellow color of the residual current actuation indicator) means that it
is working properly.
Installation
RCCBs are installed on a 35 mm wide mounting rail (DIN rail) in switch-boards
with a degree of protection according to IEC 60529 not less than IP30.
Once in 6 months to tighten the contact screw clamps.
Only qualified electrical personnel should carry out installation, connection and
commissioning of RCCBs.
After installation and checking its correctness, supply the voltage of the
electrical network to the electrical installation and turn on the RCCB by mo-ving the
control handle to the "I" "ON" position, press the "TEST" button.
b) if the RCCB is not cocked, then this means that the electrical installation has
a defect in the insulation of any electrical receiver, electrical wiring, wiring of the
switchboard or RCCB is faulty.
if the RCCB continues to pickup when the electrical receivers are
disconnected, it is necessary to call a qualified specialist to determine the nature of
the electrical installation damage or to identify the RCCB malfunction.
It is recommended to check the performance of the RCCB once a quarter.
The test is carried out by pressing the "TEST" button. Immediate actuation of
the RCCB and disconnection of the protected electrical installation mean that the
RCCB is working properly.
In this case, you must perform the following actions:
turn off all electrical receivers and cock the RCCB. If the RCCB is cocked,
then this indicates the presence of an electrical receiver with damaged insulation.
The malfunction is detected by serial connection of electrical receivers until the
RCCB is triggered. The damaged electrical receiver should be disconnected.
Check the RCCB operability by pressing the "TEST" button;
Warranty period of RCCB – 10 years from the date of sale to the consumer,
under observance of that the consumer meets the requirements of transportation,
storage and operation.
Service life and manufacturer's warranty
Service life of RCCB – 15 years.
RCCBs cannot be repaired. In case of failure, it is necessary to replace it.
Transportation of RCCBs is allowed by any type of enclosed transport in the
manufacturer's package, ensuring the protection of RCCBs from mechanical
damage, pollution and moisture ingress.
Transportation of RCCBs should be carried out at ambient temperatures from
minus 25 °Ñ to 55 °Ñ.
Storage of RCCBs is carried out in the manufacturer's package in rooms with
natural ventilation at an ambient temperature of minus 25 °Ñ to 55 °Ñ and a relative
humidity of no more than 90 % at a temperature of 20 °Ñ. Storage is allowed
at 50 % relative humidity and 40 °Ñ.
Disposal
Dispose the product by transferring the product to a specialized enterprise for
the processing of secondary raw materials in accordance with the requirements of
the legislation in the territory of sale.
Transportation and storage
Maintenance
90
90
2
М=5 N·m max
S=1,5...35 mm
2
Specifications and operating conditions (continuation)
Parameter denomination
Value for circuit-breakers of type
R10N of AC type
R10N of A type
Operating temperature range, °Ñ
From minus 25 to 45
Relative air humidity at the temperature 20 °Ñ, %
90
Sinusoidal vibration
Frequency range, Hz
0,5–100
Maximum acceleration
-2
amplitude, m·s (g)
5 (0,5)
Repeated impacts
Maximum shock acceleration
-2
peak value, m·s (g)
30 (3)
Duration of impact
acceleration, ms
2–20
Operation mode
continuous
Version 2
1
86
753N
Т
N 4
4N
3N
Т