UPS for prolonged
power supply
The three-stage switch of charging current enables the user to connect batteries of dierent
capacities depending on the required time to provide the power backup. It is recommended
forthebattery with the capacity 20–50 А·h to use the position L (3–5 A) of the switch, withtheca-
pacity 50–100А·h touse the position M (7–9 A), with the capacity 100–200 А·h to use the position
Н (13–15 A).
Recommendations regarding selection of batteries
Select the capacity of a battery (batteries) depending on the connected load power and re-
quired time of power standby, see the table 1 below. Based on the selected capacity, choose
acertain battery (batteries).
Storage conditions of batteries must conform to the requirements of the battery producer.
Table 1. Selection of batteries
RT-1000
RT-500
Battery
capacity
Load
100 W
Load
200 W
Load
300 W
Load
400 W
Load
480 W
Load
500 W
Load
600 W
12V/50 А·h 3 h 1.5 h 0.7 h 0.5 h 0.4 h 0.4 h 0.3 h
12V/75 А·h 5 h 2.3 h 1.5 h 1 h 0.8 h 0.8 h 0.5 h
12V/100 А·h 7 h 3 h 2 h 1.5 h 1 h 1 h 0.7 h
12V/150 А·h 12 h 5 h 3 h 2 h 1.5 h 1.5 h 1 h
12V/200 А·h 15 h 7 h 4.5 h 3 h 2.5 h 2.5 h 2 h
We recommend to use SVEN SV12170, SVEN SV12500, SVEN SV121000 batteries.
Notes. When two or more batteries are used, they should be of one type and have the same capac-
ity (if their capacities are dierent, the batteries will have dierent internal resistance and due
to this the charge level will be dierent). Batteries should be connected in parallel, when several
batteries are used simultaneously. Additional cables (to be purchased separately) will be required
to connect extra batteries. When two or more batteries areconnected, theplus terminal of one
battery is connected to the plus terminal of the other battery, minus terminals of batteries are con-
nected similarly. The connecting cables must have a sucient cross-section and a minimum length.
Features
Continuous action with prolonged back-up time.
Built-in automatic voltage regulator.
Pure Sine Wave.
Microprocessor control.
Protection against short circuit in connected load to UPS, as well as against overload.
Protection against overvoltage or undervoltage in the mains.
IP-20 ingress protection.
Three-stage switch of charging current.
Self-diagnosis after switching on.
Indication of operation modes on LCD display.
Mode switchover time 8 msec.
Automatic start function.
Low noise level.