9.4 Cleaning
If necessary, the filter bowl and the filter can be cleaned.
1. Close shutoff valve on inlet
2. Release pressure on outlet side (e.g. through water tap)
3. Close shutoff valve on outlet
4. Unscrew filter bowl
o Use double ring wrench ZR06F
5. Remove filter, clean and reinsert
6. Place O-ring onto filter bowl
7. Screw in filter bowl hand-tight (without tools)
8. Slowly open shutoff valve on inlet
9. Slowly open shutoff valve on outlet
10. Disposal
• Dezincification resistant brass housing
• Brass threaded connections
• High-quality synthetic material valve insert
• High-quality synthetic material spring bonnet with adjust-
ment knob and setting scale
• Spring steel adjustment spring
• Stainless steel fine filter
• Red-bronze or shock-resistant, clear transparent synthetic
material filter bowl
• Fibre-reinforced NBR diaphragm
•NBR seals
Caution !
Do not use any cleaning agents containing solvents
and/or alcohol to clean the plastic parts!
Frequency: every 6 month (depending on local opera-
ting conditions)
To be carried out by an installation company
Detergents must not be allowed to enter the environ-
ment or the sewerage system!
Observe the local requirements regarding correct waste
recycling/disposal!
11. Troubleshooting
Problem Cause Remedy
Beating sounds Filter combination is toolarge Call our Technical Customer Services
Water is escaping from the spring
bonnet
Diaphragm in valve insert is faulty Replace valve insert
Too little or no water pressure Shutoff valves upstream or downstream
from filter not fully open
Open the shutoff valves fully
Filter combination is not set to the
desired outlet pressure
Set outlet pressure
Filter mesh dirty Clean or replace filter
Not fitted in flow direction Fit filter in flow direction (note direction of arrow
on housing)
The outlet pressure set does not
remain constant
Filter mesh dirty Clean or replace filter
Valve insert, sealing ring or edge of
nozzle is contaminated or worn
Replace valve insert
Rising pressure on outlet (e.g. in boiler) Check check valve, safety group etc.
Похожие устройства
- Honeywell ff06-1"aam 1075h Инструкция по эксплуатации
- Honeywell ff06-3/4"aaм 1074h Инструкция по эксплуатации
- Honeywell ff06-1/2"aam 1073h Инструкция по эксплуатации
- Honeywell ff06-1"aa 1072h Инструкция по эксплуатации
- Honeywell ff06-3/4"aa 1071h Инструкция по эксплуатации
- Honeywell ff06-1/2"aa 1070h Инструкция по эксплуатации
- Honeywell d06f-1"b Инструкция по эксплуатации
- Honeywell d06f-1"a Инструкция по эксплуатации
- Honeywell d06f-3/4"b Инструкция по эксплуатации
- Honeywell d06f-3/4"a Инструкция по эксплуатации
- Honeywell d06f-1/2"b Инструкция по эксплуатации
- Honeywell d06f-1/2"a Инструкция по эксплуатации
- Hosseven hdu-3 dk Инструкция по эксплуатации
- Hosseven hhs-9v fan Инструкция по эксплуатации
- Hosseven hdu-3 Инструкция по эксплуатации
- Hosseven hdu-5 dkv fan Инструкция по эксплуатации
- Hosseven hdu-5 dk Инструкция по эксплуатации
- Hosseven hdu-3 dkv fan Инструкция по эксплуатации
- Hosseven hs-8 Инструкция по эксплуатации
- Hosseven hp-5 Инструкция по эксплуатации