Honeywell fk06-1/2"aa 1076h Инструкция по эксплуатации онлайн [8/18] 194594

Honeywell fk06-1/2
MU1H-1126GE23 R0609 8 Honeywell GmbH
GB
9.4 Cleaning
If necessary, the filter bowl and the filter can be cleaned.
1. Close shutoff valve on inlet
2. Release pressure on outlet side (e.g. through water tap)
3. Close shutoff valve on outlet
4. Unscrew filter bowl
o Use double ring wrench ZR06F
5. Remove filter, clean and reinsert
6. Place O-ring onto filter bowl
7. Screw in filter bowl hand-tight (without tools)
8. Slowly open shutoff valve on inlet
9. Slowly open shutoff valve on outlet
10. Disposal
Dezincification resistant brass housing
Brass threaded connections
High-quality synthetic material valve insert
High-quality synthetic material spring bonnet with adjust-
ment knob and setting scale
Spring steel adjustment spring
Stainless steel fine filter
Red-bronze or shock-resistant, clear transparent synthetic
material filter bowl
Fibre-reinforced NBR diaphragm
•NBR seals
Caution !
Do not use any cleaning agents containing solvents
and/or alcohol to clean the plastic parts!
Frequency: every 6 month (depending on local opera-
ting conditions)
To be carried out by an installation company
Detergents must not be allowed to enter the environ-
ment or the sewerage system!
Observe the local requirements regarding correct waste
recycling/disposal!
11. Troubleshooting
Problem Cause Remedy
Beating sounds Filter combination is toolarge Call our Technical Customer Services
Water is escaping from the spring
bonnet
Diaphragm in valve insert is faulty Replace valve insert
Too little or no water pressure Shutoff valves upstream or downstream
from filter not fully open
Open the shutoff valves fully
Filter combination is not set to the
desired outlet pressure
Set outlet pressure
Filter mesh dirty Clean or replace filter
Not fitted in flow direction Fit filter in flow direction (note direction of arrow
on housing)
The outlet pressure set does not
remain constant
Filter mesh dirty Clean or replace filter
Valve insert, sealing ring or edge of
nozzle is contaminated or worn
Replace valve insert
Rising pressure on outlet (e.g. in boiler) Check check valve, safety group etc.
Скачать