5) Vacuuming from liquid pipe and gas pipe at the same time.
Special vacuum dry procedure (this vacuum dry method is used if there s mois-
ture when  ushing the refrigerant pipe or rainwater may enter into the pipe):
1) Vacuum dry (for the  rst time) — connect the all-purpose detector to the inlet
of liquid pipe and gas pipe, and run the vacuum pump more than two hours (the
vacuum pump should be below –755mmHg).
2) Fill nitrogen to 0.5Kgf/cm
2
. Because nitrogen is for drying gas, it has vacuum
drying e ect during vacuum destroy. But if the moisture is too much, this me-
thod can t dry thoroughly. So, please pay more attention to prevent water entering
and forming condensation water.
3) Run the vacuum pump more than one hour (the vacuum pump should be
below –755mmHg). If the pump can’t achieve –755mmHg after pumping two
hours, repeat procedure 2 and 3.
4) Vacuum placement test: place 1 hour when it achieves –755mmHg, pass if the
vacuum watch shows no rising. If it rises, it shows theres moisture or leakage
point.
7.3.4. Additional refrigerant charge
Refrigerant cannot be charged until  eld wiring has been completed.
Refrigerant may only be charged after performing the leak test and the vacuum
pumping.
When charging a system, care shall be taken that its maximum permissible
charge is never exceeded, in view of the danger of liquid hammer.
Charging with an unsuitable substance may cause explosions and accidents, so
always ensure that the appropriate refrigerant is charged.
Always use protective gloves and protect your eyes when charging refrigerant.
The outdoor unit is factory charged with refrigerant. Calculate the added re-
frigerant according to the diameter and the length of the liquid side pipe of the
outdoor unit/indoor unit.
Table 7.3.4.
D(mm)
L(m)
6.4 9.5 12.7
Less than 5m
Over 5 m 11 g/m 30 g/m 60 g/m
Remark:
L (m): The length of the refrigerant pipe (one-way)
D (mm): Liquid side piping diameter