Toshiba MMK-AP0123H — инструкция по снятию и установке PMV мотора [134/152]

Toshiba MMK-AP0123H Инструкция по эксплуатации онлайн [134/152] 278767
134
No.
S
Part name
PMV motor
Procedures
<Cautions at work>
Using spanners by 17mm and 19mm, remove the
PMV motor. <AP0243 to AP0153>
Using spanners by 16mm and 19mm, remove the
PMV motor. <AP0123 to AP0073>
To avoid deformation of the pipes, do not use a
monkey wrench. In case that the clearance to the
ceiling is 110, use a spanner with length by 150
mm or shorter.
1) Perform work of item
Q
.
2) Perform work of item
R
.
3) Remove the bundling band of PMV motor lead
wire.
4) Pull off butyl of PMV main unit until the position
shown in the right photo.
5) Using a spanner, remove PMV.
<Caution in reassembling>
Determine PMV motor lead wire drawing-out
position as same as that before removing.
Return butyl rubber to the original position.
Remarks
<AP0243 to AP0153>
Spanner push-in part
(Main unit side: 17 mm)
Butyl rubber Spanner push-in part
(Motor side: 19 mm)
MAX 150
MAX 160
110 mm
or more
Spanner push-in part
(Main unit side: 16 mm)
Butyl rubber Spanner push-in part
(Motor side: 19 mm)
<AP0123 to AP0073>
T
Horizontal
louver
1) Remove shaft of the horizontal louver from the
back body. (First remove the left shaft, and then
remove other shafts while sliding the horizontal
louver leftward.)