ARP_ARG Rev03 05-2013 pag. 56
7.6 USE
- Press the key to display the set-point and change it if necessary;
press the key just once to display the set temperature, which can be changed by pressing and holding
for 3 sec the same key and then using the up and down arrow keys.
- A manual defrost can be selected; press and hold for 3 sec the key and if the evaporator temperature is
no higher than +8°C, a manual defrost phase is activated. This phase ends either when the time of 30’ has
elapsed or when the temperature measured by the evaporator sensor is (+8°C). The automatic defrost,
managed by the thermostat, takes place once every 6H for a max. of 30’ during which time the readout dEF is
shown on the display.
- With the keypad active, press keys and just once to display the maximum and minimum temperature
respectively, which are recorded by the sensor inside the cabinet. The displayed values are preceded by the
readouts LO and HY respectively. To reset this stored value, press and hold for 3 sec the key at the
time it is displayed. On the display this reset is preceded by the readout RST (reset).
7.6.1 SPECIAL USE
- With the keypad active, press and hold for 3 sec the key to activate the CONTINUOUS CYCLE phase.
This phase lasts (1H) at a temperature ( -2°C (TN) and -25°C (BT) ). These values are factory set in the
controller. Unlike the normal refrigerating phase, in this case the symbol on the display is lit. When the set
time (1H) has elapsed, the symbol will go out and the appliance will start once again to operate with the
previous set point.
7.6.2 LONG IDLE PERIODS
Turn the machine OFF by pressing for three seconds, then unplug.
Clean the machine thoroughly (see paragraph 8.2) and make sure the door is left open at the end of the operation and
throughout the idle period.