21
NOTE 2: After turning off the UPS, please be aware that the UPS is working at Bypass mode and
there is risk of power loss for connected devices.
2) In Bypass mode, output voltage of the UPS is still present. In order to cut off the output, switch off
the input breaker and bypass breaker (only available for 30KVA model). A few seconds later, there
is no display shown on the display panel and UPS is complete off.
8. Turn off the UPS without utility power supply in Battery mode
1) Turn off the UPS by pressing “OFF” button for at least 0.5s, and then the buzzer will beep once.
2) Then UPS will cut off power to output and there is no display shown on the display panel.
9. Mute the buzzer
1) To mute the buzzer, please press the “Mute” button for at least 0.5s. If you press it again after the
buzzer is muted, the buzzer will beep again.
2) Some warning alarms can’t be muted unless the error is fixed. Please refer to section 3-3 for the
details.
10. Operation in warning status
1) When Fault LED flashes and the buzzer beeps once every second, it means that there are some
problems for UPS operation. Users can get the warning indicator from LCD panel. Please check the
trouble shooting table in chapter 4 for details.
2) Some warning alarms can’t be muted unless the error is fixed. Please refer to section 3-3 for the
details.
11. Operation in Fault mode
1) When Fault LED illuminates and the buzzer beeps continuously, it means that there is a fatal error in
the UPS. Users can get the fault code from display panel. Please check the trouble shooting table
in chapter 4 for details.
2) Please check the loads, wiring, ventilation, utility, battery and so on after the fault occurs. Don’t try
to turn on the UPS again before solving the problems. If the problems can’t be fixed, please contact
the distributor or service people immediately.
3) For emergency case, please cut off the connection from utility, external battery, and output
immediately to avoid more risk or danger.
12. Operation of changing battery numbers
1) This operation is only available for professional or qualified technicians.
2) Turn off the UPS. If the load couldn’t be cut off, you should remove the cover of maintenance
bypass switch on the rear panel and turn the maintenance switch to “BPS” position first.
3) Switch off the input breaker and bypass breaker (only available for 30KVA model). Then, switch off
the battery breaker (only available for long-run model).
4) Remove the cabinet cover, and disconnect battery wire for standard model. Then, please modify the
jumper of JS3 on the control board for 10KVA/15KVA/20KVA models or on INV control board for
30KVA model to set the battery numbers as following table.
Note:1 = connect with jumper; 0 = no jumper; x = the pins are for other functions.
5) Modify the battery pack for the setting number carefully. After complete it, put the cover back,
switch on the battery breaker for long-run model.
6) Switch on the input breaker and bypass breaker (only available for 30KVA model). Then, the UPS
Battery Number
in series
JS3
pin1 & pin2
pin3 & pin4
Pin5 & pin6
pin7 & pin8
18
1
0
0
X
19
0
1
0
X
20
0
0
1
X
Содержание
- Table of contents p.3
- 1 transportation and storage p.4
- Safety and emc instructions p.4
- 3 installation p.4
- 2 preparation p.4
- Connection warnings p.5
- 6 standards p.6
- 5 operation p.6
- Installation and operation p.7
- Diagram1 10k 10kl rear panel diagram 2 15kl 20kl rear panel p.7
- 2 rear panel view p.7
- 1 unpacking and inspection p.7
- Output terminal p.10
- Input output terminal p.10
- Diagram 15 battery pack rear panel p.10
- Diagram 13 15kr l 20kr l rear panel diagram 14 15kr l 20k l p.10
- Diagram 11 10kr l rear panel diagram 12 10kr l input p.10
- 3 single ups installation p.11
- 4 ups installation for parallel system p.14
- Wiring diagram of parallel system for 10k 10kl p.15
- Wiring diagram of parallel system for 15k l 20k l p.16
- Wiring diagram of parallel system for 30k p.17
- Share current cable connection p.18
- Parallel communication port connection p.18
- For optimal computer system protection install ups monitoring software to fully configure ups shutdown p.19
- 5 software installation p.19
- 4 single ups operation p.22
- 3 audible alarm p.22
- 5 parallel operation p.25
- 6 abbreviation meaning in lcd display p.26
- 7 lcd setting p.27
- 8 operating mode status description p.37
- 9 fault code p.42
- 10 warning indicator p.43
- Utility extremely unbalanced p.43
- Bypass unstable p.43
- 11 warning code p.43
- Trouble shooting p.44
- Storage and maintenance p.46
- 2 maintenance p.46
- 1 storage p.46
- Specifications p.47
Похожие устройства
-
FSP Proline 3/3 30KИнструкция по эксплуатации -
FSP Proline 3/3 20KИнструкция по эксплуатации -
FSP Proline 3/3 15KИнструкция по эксплуатации -
FSP Proline 3/3 10KИнструкция по эксплуатации -
FSP Proline 3/1 30KИнструкция по эксплуатации -
FSP Proline 3/1 20KИнструкция по эксплуатации -
FSP Proline 3/1 10KИнструкция по эксплуатации -
FSP Knight PRO + RM 6KИнструкция по эксплуатации -
FSP Knight PRO + RM 10KИнструкция по эксплуатации -
FSP Knight PRO+ 1KИнструкция по эксплуатации -
FSP Knight PRO+ 2KИнструкция по эксплуатации -
FSP Knight PRO+ 3KИнструкция по эксплуатации
Узнайте, как правильно отключить ИБП, управлять режимами и устранять неисправности. Полезные советы для безопасной эксплуатации и обслуживания.