Cabinet design and EMC for components, Blocksize format
9.7 Protective connection and equipotential bonding
Manual
Manual, 01/2011, 6SL3097-4AC10-0BP2
265
When installing components on standard mounting rails, the data listed in the table also
apply to the equipotential bonding. If only smaller connection cross-sections are permissible
at the components, then the largest possible cross-section should be used, e.g. 6 mm
2
for
SMC. These requirements also apply to distributed components located outside the control
cabinet.
CAUTION
An equipotential bonding conductor with a cross-section of at least 25 mm² must be used
between components in a system that are located at a distance from each other. If an
equipotential bonding conductor is not used, high leakage currents that could destroy the
Control Unit or other PROFIBUS nodes can be conducted via the PROFIBUS cable.
No equipotential bonding conductors are required for PROFIBUS inside a control cabinet.
For PROFIBUS connections between different buildings or parts of buildings, an
equipotential bonding must be laid parallel to the PROFIBUS cable. The following cross-
sections must be observed in accordance with IEC 60364-5-54:
Copper 6 mm²
Aliminium 16 mm²
Steel 50 mm²
For more information about equipotential bonding for PROFIBUS, see:
http://www.profibus.com/fileadmin/media/wbt/WBT_Assembly_V10_Dec06/start.html
NOTICE
If the above information about equipotential bonding is not taken into account, this can
cause the field bus interfaces to malfunction or devices to malfunction.
Note
PROFINET
For installation guidelines and information of protective grounding and equipotential bonding
for all PROFINET types and topologies, refer to DOWNLOADS at:
http://www.profibus.com