Daikin ZH5WLGV Инструкция по эксплуатации IV ver онлайн [16/58] 527100

Daikin ZH5LMGU Инструкция по эксплуатации IV ver онлайн [16/58] 527077
Si50-402 Overhaul Instructions
Semi-Hermetic Single Screw Compressor Version IV 15
(5) Turn the gate rotor shaft to remove it from the screw rotor. Be careful not to damage the
gate rotor.
5. Removing and Installation of Gate Rotor
(1) Remove C type retaining ring.
(2) Remove the gate rotor from the shaft.
(3) Apply red check to the gate rotor, and check that the rotor is free of cracks.
If the rotor is found cracked, replace it with a new one.
(4) Install the gate rotor on the shaft, and mount the C-type retaining ring.
The gate rotor has front and back sides. Position the gate rotor so that the manufacturing
number is visible.
6. Removing The Suction End Cover
(1) Remove all the mounting bolts.
(2) Mount guide bolts in two bolt holes on the upper section.
(Be sure to mount guide bolts, since the suction end cover is heavy.)
(3) In the guide bolt holes, thread the bolts that were removed previously, then remove the
suction cover from the casing.
Locate positioning pins at two locations, and screw them.
Fig. 4-9 Removing suction end cover