Daikin EWWH955DZXEA2 Инструкция по монтажу онлайн [18/32] 533214

Daikin EWWH955DZXEA2 Инструкция по монтажу онлайн [18/32] 533214
D-EIMWC01405-18EN- 18/32
Water flow switch interlock terminals are included in the controller. See the wiring diagram for the correct connections on
the field.
The purpose of the water flow switch interlock is to prevent the compressor from running for enough time to let the two
evaporator and condenser water pumps to operate and ensure the correct water flow. The flow switch can be supplied on
request from Daikin Applied Europe and in any case must be compulsorily installed on the machine. For better protection
against freezing, connecting the evaporator flow switch, connect free contact or pump circuit breaker contact in series.
It is best to leave pump control to the microprocessor for better system management.
If an external system independently manages pump start, follow this logic.
Evaporator water inlet
turn on the pump 2 minutes before enabling the machine
turn off the pump 5 minutes after disabling the machine
Condenser water pumps:
turn the pump on 30 seconds before enabling the machine
turn the pump off 1 minute after the last compressor is turned off.

Содержание

Скачать