ESiE04-03 Functional Description
Part 2 – Functional Description 2–19
3
2
4
5
1
Fan status during
defrost
The table below shows the fan status during defrost.
(1)
: This fan status is kept during the complete defrost cycle, independent from T
amb
changes.
Illustration start
condition
The illustration below shows the start conditions and defrost activition ranges for the defrost function.
Legend start
condition
The table below describes the patterns used in the start condition illustration above.
Fan defrost
setting
Fan status K4A K5A K12A
Fan defrost 1
M11F: OFF
M12F: OFF
M21F: OFF
M22F: OFF
Open Open Open Depending
on
dipswitch
Fan defrost 2 T
amb
at defrost start time
= > 5°C
M11F: Medium
M12F: OFF
M21F: Medium
M22F: OFF
(1)
Open Closed Open
T
amb
at defrost start time
< 5°C
M11F: OFF
M12F: OFF
M21F: OFF
M22F: OFF
(1)
Open Open Open
-8
-1
0
-10
T
coil
(°C)
Start condition 2B (Accumulate Timoperate)
Start condition 1 & 2A (Reset Timconditional)
Start condition 1 & 2A (Start Timconditional)
Max. 50°C
(= basic no limit)
A °C (5=°C)
T
ambient
(°C)
Pattern Description
Defrost activation range of start condition 2B
After defrost allowed timer (= 30 min + 2 h acc)
Defrost activation range of start condition 2B
Without allowed timer (= 2 h acc)
Defrost activation range of start condition 1/2A
Without allowed timer (= 150 s)
Defrost activation range of start condition 1/2A
After defrost allowed timer (= 30 min + 150 s)