Wiring Layout ESiE04-03
1–78 Part 1 – System Outline
3
11
4
5
Dipswitches and
pushbuttons
The illustration below shows the dipswitches and pushbuttons on the PCB.
Function The table below describes the function of the dipswitches and pushbuttons on the PCB.
LED’s The table below describes the LEDs.
Status H1P and H2P The table below describes the status of H1P and H2P.
1 2 3
S1A
4 1 2
S2A
S1A Dipswitch 1 S2A Dipswitch 2
1 0 = 1 circ.
1 = 2 circ.
1 Defrost setting (only for
EUWY*5-24KAZW1)
0 = Start condition 1 & fan defrost 1
(5HP, 8HP, 16HP)
1 = Start condition 2A/B & fan defrost 2
(10HP, 12HP, 20HP, 24HP)
2
3
4
010 = EUWA
100 = EUWY (without defrost com-
pressor stop)
101 = EUWY (with defrost
compressor stop)
2 Fan setting
0 = Fan setting 1
(5HP, 8HP, 16HP)
1 = Fan setting 2
(10HP, 12HP, 20HP, 24HP)
Symbol LED Meaning
HAP Light emitting diode
(Service monitor - Green)
Blinking = CPU OK
Not blinking = CPU NOK
H1P Light emitting diode
(Service monitor - RED)
-
H2P Light emitting diode
(Service monitor - RED)
-
Meaning H1P H2P
No error OFF OFF
Safety device ON OFF
Reverse phase OFF ON
Sensor broken ON ON