ESiE04-03 Troubleshooting
Part 3 – Troubleshooting 3–31
33
4
5
1
Fans The table below contains the settings of the fans.
Anti-freeze and
supporting heaters
The table below contains the settings of the anti-freeze and the supporting heaters.
Alarm The table below contains the settings of the alarm.
cb User Maintenance threshold of c9 & cA 0 h x 100 0 h x 100 r/w
cv Direct Running hours pump __ __ r
Code Parameter Function
EUWA*5-
12KAZW1
EUWA*16-
24KAZW1
Read/
write
Code Parameter Function EUWA*5-24KAZW1
Read/
write
f1 Factory Are there any fans? 0 r/w
Code Parameter Function
EUWA*5-
12KAZW1
EUWA*16-
24KAZW1
Read/
write
a1 Factory Anti-freeze alarm set
point
Standard 4°C 4°C r/w
ZL option -11.5°C -11.5°C
ZH option -6.5°C -6.5°C
a2 Factory Anti-freeze alarm hysteresis 3.5°C 3.5°C
a3 Factory Bypass time for anti-freeze alarm 0 s 0 s
a4 Factory Anti-freeze heater set
point
Standard 4°C 4°C
ZL option -10°C -10°C
ZH option -5°C -5°C
a5 Factory Anti-freeze heater hysteresis 3°C 3°C
a6 Factory Supporting heaters probe 0 0
a7 Factory Limit anti-freeze alarm set -15°C -15°C
Code Parameter Function
EUWA*5-
12KAZW1
EUWA*16-
24KAZW1
Read/
write
p1 Factory Flow-start timer 20 s 20 s r/w
p2 Factory Flow-stop timer 5 s 5 s
p3 Factory LP bypass timer 60 s 60 s
p4 User Buzzer ON time 1 min 1 min
p5 Factory Reset of alarms 0 0
p8 Factory Selection of digital input ID1 1 1