Troubleshooting ESiE04-03
3–36 Part 3 – Troubleshooting
3
1
3
4
5
Compressor The table below contains the settings of the compressor.
Fans The table below contains the settings of the fans.
Fan control is done by the I/O PCB.
Defrosting The table below contains the settings for defrosting.
Code Parameter Function
EUWY*5-
12KAZW1
EUWY*16-
24KAZW1
Read/
write
c1 Factory Min. running time 0 s 0 s r/w
c2 Factory Guard timer 6 (x 10 s) 6 (x 10 s)
c3 Factory Anti-recycling timer 24 (x 10 s) 24 (x 10 s)
c4 Factory Start delay between the two
compressors
__ 5 s
c5 Factory Stop delay between the two
compressors
__ 0 s
c6 User Time-delay at start-up 0 s 0 s
c7 User ON delay pump-compressor 15 s 15 s
c8 User OFF delay pump-compressor 0 min 0 min
c9 Direct Running hours compressor 1 __ __ r
ca Direct Running hours compressor 2 __ __
cb User Maintenance threshold of c9 & cA 0 h x 100 0 h x 100 r/w
cv Direct Running hours pump __ __ r
Code Parameter Function EUWY*5-24KAZW1
Read/
write
f1 Factory Are there any fans? 0 r/w
Code Parameter Function EUWY*5-24KAZW1
Read/
write
d1 Factory Defrost cycle 1 r/w
d2 Factory Time or temperature based defrost 1
d3 Factory Defrost starting temperature 8.5°C
d4 Factory Defrost stopping temperature 11.5°C
d5 Factory Min. time interval for defrost start 10°C
d6 Factory Min. duration of defrost cycle 10°C
d7 Factory Max. duration of defrost cycle 10 min
d8 Factory Time delay between 2 defrost cycles 20 min
db Factory Anti-freeze heaters active while
defrosting
0