Functional Description ESiE04-03
2–6 Part 2 – Functional Description
3
1
2
4
5
Legend The table below describes the patterns and abbreviations used in the operational range illustration
above.
Pattern/
Abbrevia-
tion
Description
Standard operation
Pull-down area
Protection water circuit against freezing
If the units operate below -5°C and are installed in a draughty space, a windscreen is
required
ZH Option to produce evaporating leaving water temperature till -5°C
ZL Option to produce evaporating leaving water temperature till -10°C