6 English
•
Refer to Table 1 for tightening torque.
Table 1
CAUTION
Overtightening may damage the flare and cause leaks.
Be careful for oil not to adhere to any portions other
than a flare part. If oil adhere to resin parts etc., there is
a possibility of damaging by deterioration.
•
Refer to Table 2 if no torque wrench is available.
Using a wrench to tighten flare nuts causes the tightening
torque to suddenly grow much tighter after a certain point.
From there, tighten the nut further by the appropriate angle
listed in Table 2.
(2)
After the work is finished, make sure to check that
there is no gas leak.
(3)
After checking for gas leaks, be sure to insulate the
pipe connections referring to Fig. 8.
•
Insulate using the insulation for fitting (3) (4) included with
the liquid and gas pipes. Besides, make sure the insula-
tion for fitting (3) (4) on the liquid and gas piping has its
seams facing up.
(Tighten both edges with clamp (9).)
•
For the gas piping, wrap the mid. sealing pad (6) over the
insulation for fitting (4) (flare nut part).
CAUTION
Be sure to insulate any field piping all the way to the piping
connection inside the unit. Any exposed piping may cause
condensation or burns if touched.
•
When brazing the refrigerant piping, perform nitrogen
replacement first, or perform the brazing (CAUTION 2) while
feeding nitrogen into the refrigerant piping (CAUTION 1), and
finally connect the indoor unit using the flare connections.
(Refer to Fig. 9)
CAUTION
1. When brazing a pipe while feeding nitrogen inside the
pipe, make sure to set the nitrogen pressure to 0.02 MPa
(0.2 kg/cm
2
) using the pressure reducing valve. (This
pressure is such that breeze is blown to your cheek.)
2. Do not use a flux when brazing the refrigerant pipe joints.
Use phosphor copper brazer (BCuP-2: JIS Z 3264/B-
Cu93P-710/795: ISO 3677) which does not require flux.
(Using a flux containing chlorine may cause the piping to
corrode. Using a welding flux containing fluorine may
cause the refrigerant lubricant to deteriorate, and affect
adversely the refrigerant piping system.)
Not recommendable but in case of emergency
You must use a torque wrench but if you are obliged to install the
unit without a torque wrench, you may follow the installation
method mentioned below.
After the work is finished, make sure to check that there is
no gas leak.
When you keep on tightening the flare nut with a spanner, there
is a point where the tightening torque suddenly increases. From
that position, further tighten the flare nut the angle shown below:
Table 2
Pipe
size
Tightening torque
Flare dimen-
sion A (mm)
Flare shape
Ø6.4 15 – 17 N·m 8.7 – 9.1
Ø9.5 33 – 39 N·m 12.8 – 13.2
Ø12.7 50 – 60 N·m 16.2 – 16.6
Ø15.9 63 – 75 N·m 19.3 – 19.7
A
45
0
Ⳳ
2
0
R0.4-0.8
90
0
Ⳳ
2
0
Main unit
Wrap over the top of the
flare nut connection.
(accessory)
(accessory)
Insulation for fitting (3)
(accessory)
Liquid pipe
Fig. 8
Main unit
Attach to base
Piping insulation material
(main unit)
Piping insulation material
(Field supply)
Turn seams up
Flare nut connection
Clamp (9) (accessory)
Piping insulation material
(Field supply)
Clamp (9)
(accessory)
Liquid Piping Insulation Procedure
Gas Piping Insulation Procedure
Insulation for fitting (4)
Mid. sealing pad (6)
Turn seams up
Flare nut connection
Attach to base
Piping insulation
material (main unit)
Gas pipe
Pipe size Further tightening angle
Recommended arm
length of tool
Ø6.4 (1/4”) 60 to 90 degrees Approx. 150mm
Ø9.5 (3/8”) 60 to 90 degrees Approx. 200mm
Ø2.7 (1/2”) 30 to 60 degrees Approx. 250mm
Ø15.9 (5/8”) 30 to 60 degrees Approx. 300mm
Fig. 9
Nitrogen
Nitrogen
Hands
valve
Pressure-reducing valve
Taping
Part to be brazed
Refrigerant piping
4PEN325876-1F.book Page 6 Thursday, April 20, 2017 8:20 AM
Содержание
- Installation manual 1
- System inverter air conditioners 1
- Daikin industries czech republic s r o 2
- En60335 2 4 2
- Fxdq15a3veb fxdq20a3veb fxdq25a3veb fxdq32a3veb fxdq40a3veb fxdq50a3veb fxdq63a3veb 2
- Machinery 2006 42 ec electromagnetic compatibility 2014 30 eu 2
- P481419 1 2
- P481419 1_fxdq15 63a3veb fm page 1 monday april 24 2017 10 01 am 2
- Tetsuya baba managing director pilsen 2nd of may 2017 2
- Contents 3
- Safety precautions 3
- 1 precautions 4
- 2 accessories 4
- 3 optional accessories 4
- Before installation 4
- For the following items take special care during construction and check after installation is finished 4
- Selecting installation site 5
- Preparations before installation 6
- In case of back side in case of bottom side 7
- Indoor unit installation 7
- Refrigerant piping work 7
- Drain piping work 9
- Installing the duct 10
- 1 general instructions 11
- 2 specifications for field supplied fuses and wire 11
- 3 electrical characteristics 11
- A circuit breaker capable of shutting down power supply to the entire system must be installed 11
- All field supplied parts and materials electric works must conform to local codes 11
- All wiring must be performed by an authorized electrician 11
- Be sure to ground the air conditioner 11
- Do not the earth wire should come in contact with gas pipes water pipes lightning rods or telephone earth wires 11
- Do not turn on the power supply circuit breaker or earth leak age breaker until all other work is done 11
- Electric wiring work 11
- English 9 11
- For details on hooking up the remote controller refer to the remote controller installation manual 11
- Gas pipes gas leaks can cause explosions and fire 11
- Length of the transmission wiring and remote controller wiring 11
- Mca minimum circuit amps a mfa max fuse amps a kw fan motor output kw fla full load amps a 11
- Power related 11
- Refer to the installation manual attached to the outdoor unit for the size of power supply wiring connected to the outdoor unit the capacity of the circuit breaker and switch and wiring instructions 11
- See also the wiring diagram plate attached to the control box lid when laying electrical wiring 11
- Shows only in case of protected pipes use h07rn f in case of no protection 2 insulated thickness 1mm or more 3 if the wiring is in a place where people it can be easily touched by people install an earth leakage breaker to pre vent electric shock 4 when using an earth leakage breaker make sure to select one useful also to protection against overcurrent and short circuit when using an earth leakage breaker only for earth device make sure to use a wiring interrupter together 11
- Shut off the power before doing any work 11
- Telephone earth wire and lightning rods the ground potential when struck by lightning gets extremely high 11
- The length of the transmission wiring and remote controller wiring are as follows 11
- This system consists of multiple indoor units mark each indoor unit as unit a unit b and be sure the terminal board wiring to the outdoor unit and bs unit are properly matched if wiring and piping between the outdoor unit and an indoor unit are mismatched the system may cause a malfunction 11
- To avoid short circuiting the power supply wire be sure to use insulated terminals 11
- Use copper wire only 11
- Water pipes they cannot be grounded if hard vinyl pipes are used 11
- 1 how to connect wirings 12
- Wiring example 12
- Precautions when laying power supply wiring 13
- Wiring example 13
- 2 control by 2 remote controllers con trolling 1 indoor unit by 2 remote controllers 14
- 3 remote control forced off and on off operation 14
- 4 centralized control 14
- Field setting and test run 14
- 1 setting the static pressure selection 15
- 2 remote control setting 15
- 3 setting the filter sign display interval 15
- 4 settings for separately sold accessories 15
- Field setting and test run 15
- Field settings may have to be performed using the remote controller depending on the type of installation 15
- English 16
- Unified wiring diagram legend 16
- Wiring diagram 16
Похожие устройства
- Daikin FXDQ25A3VEB Инструкция по эксплуатации
- Daikin FXDQ25A3VEB Инструкция по монтажу
- Daikin FXDQ25A3VEB Технические данные
- Daikin FXDQ32A3VEB Инструкция по эксплуатации
- Daikin FXDQ32A3VEB Инструкция по монтажу
- Daikin FXDQ32A3VEB Технические данные
- Daikin FXDQ40A3VEB Инструкция по эксплуатации
- Daikin FXDQ40A3VEB Инструкция по монтажу
- Daikin FXDQ40A3VEB Технические данные
- Daikin FXDQ50A3VEB Инструкция по эксплуатации
- Daikin FXDQ50A3VEB Инструкция по монтажу
- Daikin FXDQ50A3VEB Технические данные
- Daikin FXDQ63A3VEB Инструкция по эксплуатации
- Daikin FXDQ63A3VEB Инструкция по монтажу
- Daikin FXDQ63A3VEB Технические данные
- MEAN WELL OWA-60E-12 Инструкция по эксплуатации
- MEAN WELL OWA-60E-12 Инструкция язык EN
- MEAN WELL OWA-60E-12 Datasheet
- MEAN WELL OWA-60E-12 Документация
- MEAN WELL OWA-60E-15 Инструкция по эксплуатации