SiENBE37-704 Specifications
Specifications 31
1-2 ELECTRICAL SPECIFICATIONS FXCQ20MV3B FXCQ25MV3B FXCQ32MV3B FXCQ40MV3B FXCQ50MV3B
Power
Supply
Name V3
Phase 1 1 1 1 1
Frequency Hz 50 50 50 50 50
Voltage V 230 230 230 230 230
Current Minimum circuit amps
(MCA)
A 0.50 0.50 0.50 0.80 0.80
Maximum fuse amps
(MFA)
A 16.00 16.00 16.00 16.00 16.00
Full load amps (FLA) A 0.40 0.40 0.40 0.60 0.60
Voltage
range
Minimum V -10%
Maximum V +10%
Power Supply Intake Both indoor and outdoor unit
Notes Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminals is not below or
above listed range limits.
Maximum allowable voltage range variation between phases is 2%.
MCA/MFA : MCA = 1.25 × FLA
MFA <= 4 × FLA
select wire size based on the MCA
instead of a fuse, use a circuit breaker
For more details concerning conditional connections, see http://extranet.daikineurope.com, select "E-Data Books".
Finally click on the document title of your choice.
1-2 ELECTRICAL SPECIFICATIONS FXCQ63MV3B FXCQ80MV3B FXCQ125MV3B
Power
Supply
Name V3
Phase 1 1 1
Frequency Hz 50 50 50
Voltage V 230 230 230
Current Minimum circuit amps
(MCA)
A 0.90 1.10 1.30
Maximum fuse amps
(MFA)
A 16.00 16.00 16.00
Full load amps (FLA) A 0.70 0.90 1.00
Voltage
range
Minimum V -10%
Maximum V +10%
Power Supply Intake Both indoor and outdoor unit
Notes Voltage range : units are suitable for use on electrical systems where voltage supplied to unit terminals is not below or
above listed range limits.
Maximum allowable voltage range variation between phases is 2%.
MCA/MFA : MCA = 1.25 × FLA
MFA <= 4 × FLA
select wire size based on the MCA
instead of a fuse, use a circuit breaker
For more details concerning conditional connections, see http://extranet.daikineurope.com, select "E-Data Books".
Finally click on the document title of your choice.