Appendix SiEN34-705
164 General Information
! When the number of indoor units to be connected to the branch pipes is less than the
number of branch pipes available for connection then cap pipes should be fitted to the
surplus branches.
! When the size of the selected field piping is different from that of branch pipe then the
connecting section should be cut with a pipe cutter as shown in the figure below.
! When field piping is connected to the B section of the inlet/outlet pipe on the outdoor unit
side of the liquid pipe header.
! Cut the B section with a pipe cutter as shown below and connect it to the A section.
! Connect the flared section of the field pipe to the B section.
! Fit the branch pipe so that the branch lies in a horizontal plane.
! The branch pipe must be insulated in accordance with the instruction manual which comes
with each kit.
1. Use the insulator included in the kit to insulate the header.
2. Joints between insulators included in the kit and those already applied to the field piping
should be sealed with the tape which is also included in each kit.
3. Any cap pipes should also be insulated using the insulator provided with each kit and then
taped as described above.
Pinched pipe
(included with kit)
Pinched pipe
(included with kit)
A section
B section
25 or more
Field pipe
Horizontal plane
View from point B in the direction of the arrow
Insulator
(included
with kit)
Gas pipe header
(included with kit)
Insulator
(included with kit)
Insulator of field pipe
Ta p e
(included
with kit)
Cap pipe
(included with kit)
Ta p e
(included with kit)
Insulator of
field pipe
(included
with kit)