8.3 Piping length and drop between the unitsi
Haier
H<=30m
h<=10 m
AU42- AU48-
l1
l2 l3
Expansion valve
l4
AS09
AS09
AS09
l 5
d
d
d
l6
AP18
1) Total length=l1+l2+l3+l4+l5+l6+2*d<=100m
2) Max. piping length of single system=(l1+l2+l3)or( l4)<=50m
3) d<=15m
4) Max. drop between outdoor unit and indoor unit: H<=30m
5) Max. drop between the two units in the same system: h<=10m
6) Max. connect capacity of one system=27300BTU/h (5HP)
7) Only wall mounted types are connected with expansion valves.
The expansion valves of different indoor models are different.
h<=10 m
Haier
AS09
l1
l2
l3
AS09
H<=30m
AS09