Provide a level concrete slab. To prevent transmission of noise or vibration, slab should not be connected
to building structure. Some sort of sound-absorbing material should be placed between the condenser
and the slab. A good material to use is rubber and cork pad.
For rooftop application, make sure the building construction can support the weight and that proper
consideration is given to the weather-tight integrity of the roof. The condensing unit contains moving
parts and can vibrate. Therefore, sound is also a consideration in rooftop applications.
6
! WARNING - Install the unit securely in a place that can bear the weight of the unit. When installed
in an insufficiently strong place, the unit could fall causing injury.
6.2.UNIT CLEARANCES
The minimum clearances for the unit are illustrated in Figure 2. Condenser air enters from three sides.
Air discharges upward from the top of the unit. Refrigerant tube and electrical connections are made
from the service access area. The most common application will find the unit best located about 10"
from back wall with connection side facing the wall. This application minimizes exposed tubing and
wiring, minimizing the space for youngsters to run around the unit with subsequent damage to the
tubing or wiring.
In more confined application spaces, such as corners provide a minimum of 10" clearance on all air
inlet sides. For service access to the compressor and control box, allow 18" minimum clearance. Ensure
top is unobstructed. If units are to be located under an overhang, there should be a minimum of 36"
clearance and provision made to deflect the warm discharge air out from the overhang.
In order to have an unrestricted air flow, owners should be advised to avoid lawn mower discharge
toward the unit depositing debris on the fin coil surface reducing the unit efficiency.
6.3.REFRIGERANT PIPING
The refrigerant piping is very important as it affects the proper operation and efficiency of the air
conditioning system. Note the following guidelines:
10" Min.
Service Access
18" Min.
Figure 2
10" Min.
10"
10"
Service Access
18" Min.
Содержание
44- Central air conditioner
- Installation operation manual
- Warning
- Table of content
- Nomenclature for model number
- Introduction
- The dimensions for the condensing unit are illustrated in figure 1 physical and electrical specifications are provided in table 1 for 10 seer systems respectively
- Table 1
- Specification
- Model hc18 60a1var s
- Model hc18 60c1var table 3
- Figure 1
- The dimensions for the condensing unit are illustrated in figure 1 physical and electrical specifications are provided in table 3 for 12 seer systems respectively
- Table 2 system cooling capacity
- The dimensions for the condensing unit are illustrated in figure 1 physical and electrical specifications are provided in table 5 for 13 seer systems respectively
- Table 6 system cooling capacity
- Table 5
- Table 4 system cooling capacity
- Model hc18 60d1var
- Unit inspection
- Installation
- Equipment protection from environment
- Liquid line does not necessarily need insulation however if they are exposed to high ambient temperatures i e kitchen boiler rooms hot attics rooftop surface then they should be insulated make sure to use the proper size tubing for the liquid line to prevent liquid refrigerant flashing to a vapor within the liquid line
- Line insulation suction line requires insulation in order to prevent condensation from forming on the piping and to prevent heat gain caused by surrounding air generally 3 8 wall thickness of armflex or equivalent is satisfactory in severe application hot high humidity areas greater thickness may be required apply the line insulation by sliding it on the sealed tuing before cutting and making connections
- Figure 3
- Do not allow the vapor line and liquid line to touch together this would cause an undesirable heat transfer resulting in capacity loss and increased power consumption
- Electrical wiring
- System startup
- Operation
- Miscellaneous
- Wh white yl yellow
- Vac common
- Use copper conductors only warning cabinet must be permanently grounded and all wiring to conform to i e c n e c c e c c l c and local codes as applicable replacement wire must be the same gage and insulation type as original wire
- Pu purple rd red vi violet
- Optional low high pressur e switches
- Line volta ge factory standard field installed optional low voltage factory standard field installed optional
- Hc18 60a1var s hc18 60c1var hc18 60d1var
- Ha cool off heat
- Compressor
- Compress or protect 3 min time delay
- Component codes bcr blower control relay bcap run capacitor blower motor cc compressor contactor cch crankcase heater optional chs crankcase heater switch optional cmpr compressor hps high pressure switch lps low pressure switch ibm indoor blower motor ofm outdoor fan motor rcap run capacitor compressor rvs reversing valve solenoid stcap start capa citor optional strly start relay optional strth start thermistor optional tran transformer 230 208 selectable
- Color codes bk black bl blue gy gray
- Br brown gr green or orange
- Air conditioner wi ring diagram
Похожие устройства
-
Haier HC60C1VARРуководство по эксплуатации -
Haier HC42C1VARРуководство по эксплуатации -
Haier HC36C1VARРуководство по эксплуатации -
Haier HC30C1VARРуководство по эксплуатации -
Haier HC60A1VARСервис мануал -
Haier HC48A1VARСервис мануал -
Haier HC42A1VARСервис мануал -
Haier HC36A1VASСервис мануал -
Haier HC30A1VARСервис мануал -
Haier HC24A1VARСервис мануал -
Haier HC18A1VARСервис мануал -
Haier HC60A1VARРуководство по эксплуатации
Узнайте, как правильно установить конденсирующий блок для кондиционера, чтобы избежать вибраций и обеспечить эффективную работу. Следуйте рекомендациям по размещению и обслуживанию.