Neola On-off DM12-01.01.07en
32 Service manual
● Moisture in the refrigerant circuit may freeze and block capillary tubing.
● Water may lead to corrosion of parts in the refrigerant system.
Therefore, the indoor units and the pipes between indoor and outdoor units must be leak tested
and evacuated to remove gas and moisture from the system.
Gas leak check (Soap water method):
Apply soap water or a liquid neutral detergent on the indoor unit connections or outdoor unit
connections by a soft brush to check for leakage of the connecting points of the piping. If bubbles
come out, the pipes have leakage.
1. Air purging with vacuum pump
1. Completely tighten the flare nuts of the indoor and outdoor units, confirm that both the 2-way and
3-way valves are set to the closed position.
2. Connect the charge hose with the push pin of handle lo to the 3-way valves gas service port..
3. Connect the charge hose of handle hi connection to the vacuum pump.
4. Fully open the handle Lo of the manifold valve.
5. Operate the vacuum pump to evacuate.
6. Make evacuation for 30 minutes and check whether the compound meter indicates -0.1Mpa. If
the meter does not indicate -0.1Mpa after pumping 30 minutes, it should be pumped 20 minutes more. If
the pressure can’t achieve -0.1Mpa after pumping 50 minutes, please check if there are some leakage
points.
Fully close the handle Lo valve of the manifold valve and stop the operation of the vacuum pump.
Confirm that the gauge needle does not move (approximately 5 minutes after turning off the vacuum
pump).
(Indoor unit)
(Liquid side)
(Gas side)
Vacuum
pump
Vacuum
pump
Lo Hi
Handle Hi
Two-way valve
Close
Manifold valve
Compound meter
Pressu
re
gauge
20Pa
Handle Lo
Charge hose
Charge hose
(Outdoor unit)
Close
Three-way valve
Содержание
- Neola on off series 1
- Service manual 2012 1
- Contents 2
- Installation 3
- Precaution 3
- Safety precaution 3
- Warning 3
- Caution 5
- Operational 6
- Function 8
- Model names of indoor outdoor units 8
- Dm12 01 1 7en neola on off 11
- Service manual 11 11
- Specification 11
- Neola on off dm12 01 1 7en 12
- Service manual 12
- Dm12 01 1 7en neola on off 13
- Service manual 13 13
- Neola on off dm12 01 1 7en 14
- Service manual 14
- Dimension 15
- Dm12 01 1 7en neola on off 15
- Indoor units 15
- Service manual 15 15
- Neola on off dm12 01 1 7en 18
- Outdoor units 18
- Service manual 18
- Capacity tables 19
- Cooling 19
- Dm12 01 1 7en neola on off 19
- Heating 19
- Service manual 19 19
- Cooling 20
- Heating 20
- Neola on off dm12 01 1 7en 20
- Service manual 20
- Cooling 21
- Dm12 01 1 7en neola on off 21
- Heating 21
- Service manual 21 21
- Cooling 22
- Heating 22
- Neola on off dm12 01 1 7en 22
- Service manual 22
- Cooling 23
- Dm12 01 1 7en neola on off 23
- Heating 23
- Service manual 23 23
- Cooling 24
- Heating 24
- Neola on off dm12 01 1 7en 24
- Service manual 24
- Refrigerant cycle diagram 25
- Indoor units 26
- Wiring diagram 26
- Outdoor units 28
- Connecting the cables 30
- Installation details 30
- Wrench torque sheet for installation 30
- Installation for the first time 31
- Pipe length and the elevation 31
- Adding the refrigerant after running the system for many years 35
- Re installation while the indoor unit need to be repaired 36
- Re installation while the outdoor unit need to be repaired 38
- Caution 41
- Come into operation and cause the unit to function abnormally 41
- Dm12 01 1 7en neola on off 41
- If air conditioner is used outside of the above conditions certain safety protection features may 41
- Maximum angle vertically to the floor and set high fan mode 41
- Operation characteristics 41
- Optimum performance will be achieved within this operating temperature 41
- Room relative humidity less than 80 if the air conditioner operates in excess of this figure the 41
- Service manual 41 41
- Surface of the air conditioner may attract condensation please set the vertical air flow louver to its 41
- Abbreviation 42
- Display function 42
- Electronic function 42
- Main protection 43
- Operation modes and functions 43
- Indoor unit error display 51
- Troubleshooting 51
- Diagnosis and solution 52
Похожие устройства
- Midea MO11D-07HN1 Инструкция по монтажу
- Midea MO11D-07HN1 Инструкция по эксплуатации
- Midea MO11D-07HN1 Технические данные
- Midea MO11D-07HN1 Сервис мануал
- Midea MO11D-09HN1 Инструкция по монтажу
- Midea MO11D-09HN1 Инструкция по эксплуатации
- Midea MO11D-09HN1 Технические данные
- Midea MO11D-09HN1 Сервис мануал
- Midea MO11D-12HN1 Инструкция по монтажу
- Midea MO11D-12HN1 Инструкция по эксплуатации
- Midea MO11D-12HN1 Технические данные
- Midea MO11D-12HN1 Сервис мануал
- Midea MO11D-18HN1 Инструкция по монтажу
- Midea MO11D-18HN1 Инструкция по эксплуатации
- Midea MO11D-18HN1 Технические данные
- Midea MO11D-18HN1 Сервис мануал
- Midea MO11D-21HN1 Инструкция по монтажу
- Midea MO11D-21HN1 Инструкция по эксплуатации
- Midea MO11D-21HN1 Технические данные
- Midea MO11D-21HN1 Сервис мануал