56 Service manual
11.2.8 Inverter compressor drive error diagnosis and solution
11.2.9 Zero crossing detection error
This is alarm signal when the main chip can’t detect over-zero signal. When such failure occurs, the
main control board must have fault.
11.2.10 Refrigerant Leakage Detection
Shut off the power supply and turn on it 5s later
The problem comes out again
Yes
Replace the T2 sensor
and check if the errors
happen again?
Is there any leakage? Especially the connection
parts, such as the gas valve and the liquid valve.
Is there cool air blowing out from the indoor air outlet?
No
No
Is there any block? (Such as the capillary or the
welded points of the pipes.)
Yes
Replace the indoor PCB
Yes
Replace the outdoor PCB
Replace inverter compressor.
Reconnect and retry
No
No
Is the connection of compressor good?
Is the wiring sequence right? The
voltage range proper?