56
Pr1
• access parameter P0
• check that the probe is intact
• check the connection system – probe
• check chiller internal temperature
Results when the error occurs with the system in “stand-by”:
• if parameter C11 is set at 0, no cycle can be activated
if parameter C11 is set at 1, the needle probe works as the chiller
compartment probe and only timer controlled cycles can be activated
Results when the error occurs during a timer controlle
d chilling cycle:
• if parameter C11 is set at 0, the cycle running is suspended
if parameter C11 is set at 1, the needle probe works as the chiller
compartment probe and blast chilling continues
Results when the error occurs during a temperature co
ntrolled chilling
cycle:
• if parameter C11 is set at 0, the cycle running is suspended
• if parameter C11 is set at 1, the probe works both as needle probe and
chiller compartment probe and blast chilling continues
Results when the error occurs during storage:
• if parameter C11 is set at 0, the compressor is managed by parameters
C4, C5 and C6
if parameter C11 is set at 1, the needle probe works as the chiller
compartment probe and storage continues
Pr2
Error in needle probe
Remedies:
• proceed as above but referring to needle probe
Results when the error occurs with the system in “stand-by”:
• only timer controlled chilling cycles can be activated
Results when the error occurs during a timer controlled chilling cycle:
blast chilling will continue
Results when the error occurs during a temperature controlled chilling
cycle:
blast chilling will continue as a timer controlled cycle
Results when the error occurs during storage:
• storage continues
8 TECHNICAL SPECIFICATIONS
8.1 Technical specifications
Casing: grey coloured and fireproof