Miniature Circuit Breaker S 200/S 200 M
Technical data and tripping characteristics
S 200 S 200 M
Installation
Terminal Failsafe bi-directional cylinder-lift terminal
Cross-section of conductors (top/bottom) solid, stranded: 35 mm
2
/ 35 mm
2
flexible: 25 mm
2
/ 25 mm
2
14 – 4 AWG
1)
Cross-section of busbars (top/bottom) 10 mm
2
/ 10 mm
2
14 – 8 AWG
2)
Torque 2.8 Nm
18 in-Ibs.
Screwdriver No. 2 Pozidrive
Mounting On DIN rail 35 mm acc. to EN 60715 by fast clip
Mounting position any
Supply optional
Dimensions and weight
Mounting dimensions acc. to DIN 43880 Mounting dimension 1
Pole dimensions (H x D x W) 88 x 69 x 17.5
Pole weight approx. 115 g
Combination with auxiliary elements
Auxiliary contact Yes
Signal/auxiliary contact Yes
Shunt trip Yes
Undervoltage release Yes
Motor Operating Device Yes
Tripping characteristics
Acc. to Tripping
characte-
ristics
Rated
current
Thermal release
3)
Electromagnetic release
4)
I
n
Currents:
conventional
non-tripping
current
I
1
conventional
tripping
current
I
2
Tripping
time
Range of
instantaneous
tripping
Tripping time
IEC/EN 60898-1 B 6 to 63 A 1.13 · I
n
1.45 · I
n
> 1 h
< 1 h
5)
3 · I
n
5 · I
n
0.1 ... 45 s (I
n
≤ 32 A)/0.1 ... 90 s (I
n
> 32 A)
< 0.1 s
C 0.5 to 63 A 1.13 · I
n
1.45 · I
n
> 1 h
< 1 h
5)
5 · I
n
10 · I
n
0.1 ... 15 s (I
n
≤ 32 A)/0.1 ... 30 s (I
n
> 32 A)
< 0.1 s
D 0.5 to 63 A 1.13 · I
n
1.45 · I
n
> 1 h
< 1 h
5)
10 · I
n
20 · I
n
0.1 ... 4 s (I
n
≤ 32 A)/0.1 ... 8 s (I
n
> 32 A)
< 0.1 s
IEC/EN 60947-2 K 0.5 to 63 A 1.05 · I
n
1.2 · I
n
> 1 h
< 1 h
5)
10 · I
n
14 · I
n
> 0.2 s
< 0.2 s
Z 0.5 to 63 A 1.05 · I
n
1.2 · I
n
> 1 h
< 1 h
5)
2 · I
n
3 · I
n
> 0.2 s
< 0.2 s
3)
The thermal releases are calibrated to a nominal reference ambient temperature; for B, C, D the reference value is 30 °C, for K and Z the reference value is 20 °C.
In the case of higher ambient temperatures, the current values fall by approx. 6 % for each 10 K temperature rise.
4)
The indicated tripping values of electromagnetic tripping devices apply to a frequency of 50/60 Hz. The thermal release operates independent of frequency.
5)
As from operating temperature (after I
1
> 1h)
1)
AWG 18 – 4 acc. to UL 486A – 486B
2)
AWG 18 – 8 acc. to UL 486A – 486B