ONNECTING THE EPO (EMERGENCY POWER OFF) OPTION
The output power can be disabled in an emergency by closing a switch connected to the EPO.
Adhere to National and local electrical codes when wiring the EPO.
The EPO switch is internally powered by the UPS for use with non-powered switch circuit breakers.
The EPO circuit is considered a Class 2 circuit, (UL, CSA standards) and a SELV circuit (IEC
standard).
Both Class 2 and SELV circuits must be isolated from all primary circuitry. Do not connect any
circuit to the EPO terminal block unless it can be confirmed that the circuit is Class 2 or SELV.
If circuit standard cannot be confirmed, use a contact closure switch.
Use one of the following cable types to connect the UPS to the EPO switch:
• CL2: Class 2 cable for general use
• CL2P: Plenum cable for use in ducts, plenums, and other spaces used for environmental air.
• CL2R: Riser cable for use in a vertical run in a floor to floor shaft.
• CLEX: Limited use cable for use in dwellings and for use in raceways.
• For installation in Canada: Use only CSA certified, type ELC (extra-low voltage control cable).
EPO
switch
Содержание
47- Installation and operation
- Smart ups rt
- English
- Surtd 3000 5000 va 200 240 vac
- Smart up
- Tower rack mount 3u
- Uninterruptible power supply
- Serial cable
- Nstallation
- Software cd
- Product documentation
- Xlt xli
- Conversion faceplate for accommodating a network management card
- By schneider electric smart up
- Specifications
- Models powerchut
- Literature kit containing
- Warranty information
- Introduction
- Ups with battery modules disconnected
- Inspect the ups upon receipt notify the carrier and dealer if there is damage
- Unpacking
- Front bezel
- Two output power cords two input power cords
- Four output power cords network management card documentation
- The packaging is recyclable save it for reuse or dispose of it properly
- Check the package contents
- The ap
- Smart ups rt user manuals cd
- Rt is a high performance uninterruptible power supply ups that provides protection for electronic equipment from utility power blackouts brownouts sags and surges the ups filters small utility line fluctuations and isolates electronic equipment from large disturbances by internally disconnecting from utility line power the ups provides continuous power from the internal battery until utility power returns to safe levels or the battery is fully discharged
- Read the safety guide before installing the ups
- Wiring and connecting the ups
- Peration
- Onfigurable
- Replacing the battery module
- Ransport
- Aintenance and
- Disconnecting the battery for transport
- Roubleshootin
- Use the table below to solve minor installation and operation problems refer to the apc web site www apc com for assistance with complex ups problems
- Nformation
- Arranty
- Service
- Limited warranty
- Apc worldwide customer support
- Requency
- Arnings
Похожие устройства
-
APC Back-UPS Pro BR1600SIРуководство по настройке -
APC Back-UPS Pro BR1200SIЭксплуатационная инструкция -
APC BX1400UIИнструкция по применению -
APC BX950UIРуководство по эксплуатации -
APC SRV3KIL-BRРуководство по настройке -
APC SRV3KIL-ARИнструкция по применению -
APC SRV3KILРуководство по настройке -
APC SRV2KIL-BRРуководство пользователя -
APC SRV2KIL-ARРуководство по эксплуатации -
APC SRV2KILИнструкция по применению -
APC SRV1KIL-BRИнструкция по работе -
APC SRV1KIL-ARЭксплуатационная инструкция
Узнайте, как правильно подключить опцию аварийного отключения питания (EPO) для безопасного отключения электроэнергии в экстренных ситуациях. Соблюдайте нормы и стандарты.