13
5000 VA models:
Terminal Mode is a menu driven interface that enables configuration of the UPS by users not using
PowerChute software or the installed Network Management Card interfaces.
Connect the serial cable to the serial port on the back of the UPS.
If PowerChute software is not installed do not perform steps 1 and 5.
1. For Windows users: STOP the PowerChute
®
Server using the following steps:
• From the Desktop, go to Start => Settings => Control Panel =>
Administrative Tools => Services.
• Select APC PowerChute Server – right click the mouse and select Stop.
1a. For Linux users: STOP the PowerChute Server using the following steps:
• Change directory to /etc/init.d.
• Initiate the command ./PowerChute stop.
2. Open a terminal program. Example: HyperTerminal
• From the Desktop, go to Start => Programs => Accessories => Communication
=>HyperTerminal.
3. Double-click on the HyperTerminal icon.
• Follow the prompts to choose a name and select an icon. Disregard the message, “...must
install a modem,” if it is displayed. Click OK.
• Select the COM port that is connected to your UPS. The port settings are:
9 bits per second - 9600
9 data - bits 8
9 parity - none
9 stop bit - 1
9 flow control - none
• Press ENTER
4. Example for setting the number of external battery packs (SURT192XLBP):
Once the blank terminal window is open, follow these steps to enter the number of battery packs:
• Press ENTER to initiate terminal mode. Press ENTER multiple times, until the prompt User
Name: is displayed. Follow the prompts. Type slowly, waiting until each character appears
on the screen prior to typing the next character.
Network Management Card defaults:
• User Name: apc
• Password: apc
• Press 1 and ENTER to select Device Manager.
• Select the model by entering the corresponding number, then press ENTER.
• Press 3 and ENTER to select Configuration.
• Press 1 and ENTER to select Battery.
Содержание
47- Installation and operation
- Smart ups rt
- English
- Surtd 3000 5000 va 200 240 vac
- Smart up
- Tower rack mount 3u
- Uninterruptible power supply
- Serial cable
- Nstallation
- Software cd
- Product documentation
- Xlt xli
- Conversion faceplate for accommodating a network management card
- By schneider electric smart up
- Specifications
- Models powerchut
- Literature kit containing
- Warranty information
- Introduction
- Ups with battery modules disconnected
- Inspect the ups upon receipt notify the carrier and dealer if there is damage
- Unpacking
- Front bezel
- Two output power cords two input power cords
- Four output power cords network management card documentation
- The packaging is recyclable save it for reuse or dispose of it properly
- Check the package contents
- The ap
- Smart ups rt user manuals cd
- Rt is a high performance uninterruptible power supply ups that provides protection for electronic equipment from utility power blackouts brownouts sags and surges the ups filters small utility line fluctuations and isolates electronic equipment from large disturbances by internally disconnecting from utility line power the ups provides continuous power from the internal battery until utility power returns to safe levels or the battery is fully discharged
- Read the safety guide before installing the ups
- Wiring and connecting the ups
- Peration
- Onfigurable
- Replacing the battery module
- Ransport
- Aintenance and
- Disconnecting the battery for transport
- Roubleshootin
- Use the table below to solve minor installation and operation problems refer to the apc web site www apc com for assistance with complex ups problems
- Nformation
- Arranty
- Service
- Limited warranty
- Apc worldwide customer support
- Requency
- Arnings
Похожие устройства
-
APC Back-UPS Pro BR1600SIРуководство по настройке -
APC Back-UPS Pro BR1200SIЭксплуатационная инструкция -
APC BX1400UIИнструкция по применению -
APC BX950UIРуководство по эксплуатации -
APC SRV3KIL-BRРуководство по настройке -
APC SRV3KIL-ARИнструкция по применению -
APC SRV3KILРуководство по настройке -
APC SRV2KIL-BRРуководство пользователя -
APC SRV2KIL-ARРуководство по эксплуатации -
APC SRV2KILИнструкция по применению -
APC SRV1KIL-BRИнструкция по работе -
APC SRV1KIL-ARЭксплуатационная инструкция
Узнайте, как настроить ИБП через терминальный режим без использования программного обеспечения. Пошаговые инструкции для пользователей Windows и Linux.