CONEL CDX 800 — подключение и защита модема для RS485 на расстоянии более 10 м [13/44]

Превью страниц Страница 13 / 44
CONEL CDX 800 [13/44] The converter must have external power supply because of galvanic separated
CDX800 DESCRIPTION
Circuit example of the meter with modem CDX 800 with data length more then 10 m:
At RS485 data cable more then 10m it is need to use over-voltage protection on CDX
800 modem side!
2.6.3. Connection of PORT2 connectors (RS485)
Panel socket RJ45.
Pin
No.
Signal
mark
Description
Data flow
direction
1 GND Signal and supply ground
2 GND Signal and supply ground
3 TxRx- RS485 B (-) Input/Output
4 TxRx+ RS485 A (+) Input/Output
5 TxRx- RS485 B (-) Input/Output
6 TxRx+ RS485 A (+) Input/Output
7 +12V EXT External power supply +10,8 ÷ +15,6V
8 +12V EXT External power supply +10,8 ÷ +15,6V
ATTENTION! External supply is for converter RS485!
The converter must have external power supply because of galvanic separated.
13
Pin 1 – ---
Pin 2 – ---
Pin 3 – RS485 (-)
Pin 4 – ---
Pin 5 – ---
Pin 6 – RS485 (+)
Pin 7 – ---
Pin 8 – ---
Modem CDX 800
SGND
RS485 (-)
RS485 (+)
Meter
SGND
RS485 (-)
RS485 (+)
Meter
1X
2X
1Y
2Y
OVPM-21