Moxa ICF-1180I-M-ST-T [12/16] Attention
![Moxa ICF-1180I-S-ST-T [12/16] Attention](/views2/1201043/page12/bgc.png)
- 12 -
Troubleshooting LED Indicators and Fiber Test
LED
Color
Description
Status/Troubleshooting
Ready
Flashing
green
Fiber diagnosis
finished
At least one converter is in Fiber
Diagnosis mode;
Check PROFIBUS master settings;
Tx and Rx cables crossed
Flashing
red
Detecting
baudrate
No PROFIBUS node;
No PROFIBUS signal received;
Tx and RX crossed over;
Baudrate setting is incorrect.
Flashing
green/red
Slot time setting
error
Recalculate the slot time; Set
TSDR ≥ 11;
Set HAS = greatest PROFIBUS
node address + 1;
Check consistency of operation
mode for DIP switch 6/7;
Check consistency of Fiber Link
Monitor Mode for DIP switch 5
P1 Flashing
red
Rx fiber cable
abnormality
Check the Rx fiber cable
connecting to this port*;
Tx and Rx cables crossed over;
Partner module is powered OFF
or
defective
Solid red
Tx fiber cable
abnormality
Check the fiber cable linking to Tx
of this port*
P2
OFF
PROFIBUS is idle
Check the PROFIBUS device
connection
Flashing
red
PROFIBUS side
error
RS-485 cable is not terminated or
only terminated at one end;
Open bus cable;
PROFIBUS D+ and D- crossed
over;
Short circuit on PROFIBUS cable;
RS-485 driver is defective;
Check slot time setting, baudrate,
and operation mode
If the abnormality indicated by the LED disappears in Fiber Diagnosis
mode, check the consistency of the DIP switch settings on all the
converters.
If the Tx and Rx cables are both abnormal, the P1 LED will shine red.
Check the Rx cable first for troubleshooting.
*If the P1 LED and P2 LED are both lit/flashing red simultaneously, the Tx
and Rx cables of P1 and P2 may be crossed.
ATTENTION
This is a Class 1 laser/LED product. Do not stare into the laser
beam.
Содержание
- Edition 7 may 2016 1
- Icf 1180i series quick installation guide 1
- Auto manual baudrate settings 2
- Introduction 2
- Why convert profibus to fiber 2
- Fiber link monitor 3
- Profibus fail safe 3
- Remote fiber diagnosis 3
- Reverse power protection 3
- Features 4
- Package checklist 4
- Mounting dimensions unit mm 5
- Attention 6
- Bottom view 6
- Front view 6
- Icf 1180i panel layouts 6
- Top view 6
- Mounting 7
- Wiring the alarm contact 7
- Attention 8
- Fiber cable 8
- Pin assignment 8
- Wiring the redundant power inputs 8
- Atex and iecex information 9
- Federal communications commission statement 9
- Slot time settings 9
- Attention 10
- Dip switch settings 10
- Led indicators 11
- Attention 12
- Troubleshooting led indicators and fiber test 12
- Fiber signal intensity diagnosis 13
- Specifications 15
Похожие устройства
- Moxa ICF-1180I-M-ST-T Технические характеристики
- Moxa ICF-1180I-S-ST Инструкция по эксплуатации
- Moxa ICF-1180I-S-ST Технические характеристики
- Moxa ICF-1180I-S-ST-T Инструкция по эксплуатации
- Moxa ICF-1180I-S-ST-T Технические характеристики
- Moxa ICF-1280I-M-ST Инструкция по эксплуатации
- Moxa ICF-1280I-M-ST Технические характеристики
- Moxa ICF-1280I-M-ST-T Инструкция по эксплуатации
- Moxa ICF-1280I-M-ST-T Технические характеристики
- Moxa ICF-1280I-S-ST Инструкция по эксплуатации
- Moxa ICF-1280I-S-ST Технические характеристики
- Moxa ICF-1280I-S-ST-T Инструкция по эксплуатации
- Moxa ICF-1280I-S-ST-T Технические характеристики
- Moxa ioLogik E1210 Инструкция по эксплуатации
- Moxa ioLogik E1210 Руководство по аппаратной части
- Moxa ioLogik E1210 Технические характеристики
- Moxa ioLogik E1210 Брошюра
- Moxa ioLogik E1210-T Инструкция по эксплуатации
- Moxa ioLogik E1210-T Руководство по аппаратной части
- Moxa ioLogik E1210-T Технические характеристики