Moxa ICF-1280I-M-ST [4/16] Features

Moxa ICF-1280I-M-ST [4/16] Features
- 4 -
Using Remote Fiber Diagnosis:
Set DIP switch SW8 to the ON position on any ICF-1280I converter and
then note the status of the Ready LED. A flashing green Ready LED
indicates that the Fiber Diagnosis has finished. The Fault LED indicates
the location of the fiber connection abnormality. The P1 or P2 LED
indicates which side (Tx or Rx) is causing the problem.
The Fault LED will shine a steady red to indicate an adjacent fiber
connection error, or flash red to indicate a non-adjacent fiber connection
error. If there are no fiber connection errors in the entire topology, the
related LEDs will shine green or remain OFF. If the fiber connection error
is adjacent to the converter, the status will also be indicated by the P1
(Port 1) or P2 (Port 2) LEDs. A flashing red light on P1 (or P2) means that
the Rx fiber cable connected to this port is broken. Similarly, a solid red
light on P1 (or P2) means that the Tx fiber cable for this port is broken.
If the fiber connection error is not adjacent to the converter (i.e., the fiber
cables connected to this converter are working properly), the Fault LED
will flash red. As a result, you should run Remote Fiber Diagnosis on every
other (second) converter in the topology to recursively troubleshoot the
problem. Further descriptions and troubleshooting can be found in the
Troubleshooting table.
Redundant Ring
The ICF-1280I series converters can connect PROFIBUS devices in a
redundant ring topology. Use the DIP switch to configure all the
ICF-1280I converters to Redundant Ring mode. When a PROFIBUS
master transmits a signal from one converter to the PROFIBUS slave
devices, this signal will travel to all the converters around the ring until it
returns to the original converter and terminate.
How to form a redundant ring topology:
To form a redundant ring topology, connect the Tx Port (Port 1) on the
first ICF-1280I converter to the Rx Port (Port 2) on the following
converter. Then, connect the Tx Port (Port 2) on the first ICF-1280I
converter to the Rx Port (Port 1) on the preceding converter. Similarly,
connect the Rx Port (Port 1) on the first ICF-1280I converter to the Tx
Port (Port 2) on the following converter. Then, connect the Rx Port
(Port 2) on the first ICF-1280I converter to the Tx Port (Port 1) of the
preceding converter.
Features
Redundant Ring mode for fiber communication backup with zero
recovery time