Moxa ioLogik E1211 [8/115] Inputs and outputs

Moxa ioLogik E1214 [8/115] Inputs and outputs
ioLogik E1200 Series Introduction
1-4
ioLogik E1210
Inputs and Outputs
Digital Inputs:
16 channels
Isolation:
3k VDC or 2k Vrms
Digital Input
Sensor Type:
Wet Contact (NPN or PNP), Dry Contact
I/O Mode:
DI or Event Counter
Dry Contact:
• On: short to GND
• Off: open
Wet Contact (DI to COM):
• On: 10 to 30 VDC
• Off: 0 to 3 VDC
Common Type:
8 points per COM
Counter Frequency:
250 Hz
Digital Filtering Time Interval:
Software configurable
Power
Requirements
Input Voltage:
12 to 36 VDC
Input Current:
110 mA @ 24 VDC
MTBF (mean time between failures)
Time:
671,345 hrs
Standard:
Telcordia SR332
ioLogik E1211
Inputs and Outputs
Digital Outputs:
16 channels
Isolation:
3k VDC or 2k Vrms
Digital Output
Type:
Sink
I/O Mode:
DO or Pulse Output
Pulse Output Frequency:
500 Hz
Over
-Voltage Protection: 45 VDC
Over
-Current Protection: 2.6 A (4 channels @ 650 mA)
Over
-Temperature Shutdown: 175°C (typical), 150°C (min.)
Current Rating:
200 mA per channel
Power Requirements
Input Voltage:
12 to 36 VDC
Input Current:
200 mA @ 24 VDC
MTBF (mean time between failures)
Time:
923,027 hrs
Standard:
Telcordia SR332