Moxa ioLogik E1213 [10/115] Iologik e1213

Moxa ioLogik E1260 [10/115] Iologik e1213
ioLogik E1200 Series Introduction
1-6
ioLogik E1213
Inputs and Outputs
Digital Inputs:
8 channels
Digital Outputs:
4 channels
Configurable DIOs (by jumper):
4 channels
Isolation:
3k VDC or 2k Vrms
Digital Input
Sensor Type:
Wet Contact (NPN or PNP), Dry Contact
I/O Mode:
DI or Event Counter
Dry Contact:
• On: short to GND
• Off: open
Wet Contact (DI to COM):
• On: 10 to 30 VDC
• Off: 0 to 3 VDC
Common Type:
12 points per COM
Counter Frequency:
250 Hz
Digital Filtering Time Interval:
Software configurable
Digital Output
Type:
Source
I/O Mode:
DO or Pulse Output
Pulse Output Frequency:
500 Hz
Over
-Voltage Protection: 41 VDC
Over
-current Protection: 1.5 A per channel @ 25°C
Over
-Temperature Shutdown: 175°C (typical), 150°C (min.)
Current Rating:
500 mA per channel
Power Requirements
Output Voltage Rating:
15 to 30 VDC (12 or 9 VDC configurable by jumper on the 4 DO channels)
Input Voltage:
12 to 36 VDC
Input Current:
130 mA @ 24 VDC
MTBF (mean time between failures)
Time:
715,256 hrs
Standard:
Telcordia SR332