Moxa ioLogik E1213 [4/8] Installation

Moxa ioLogik E1211 [4/8] Installation
- 4 -
Accuracy
±0.1% FSR @ 25°C
±0.3% FSR @ -10 and 60°C
±0.5% FSR @ -40 and 75°C
Sampling Rate (all
channels)
12 samples/second
Input Impedance
10M ohms (min.)
Built-in Resistor for
Current Input
120 ohms
Analog Output
Resolution
12 bits
Output Range
0 to 10 VDC, 4 to 20 mA
Voltage Output
10 mA (max.)
Accuracy
±0.1% FSR @ 25°C
±0.3% FSR @ -40 and 75°C
Load Resistor
Internal register: 400 ohms
Note: 24 V of external power is required when loading > 1000 ohms.
RTD
Input Type
PT50, PT100, PT200, PT500, PT1000
Resistance
1–310, 1620, 11250, 12200 ohms
Sampling Rate
12 samples/sec (all channels)
Resolution
16 bits
Accuracy
±0.1% FSR @ 25°C
±0.3% FSR @ -40 and 75°C
Input Impedance
625k ohms
Thermocouple Input
Sensor Type
J, K, T, E, R, S, B, N
Millivolt Type
±78.126 mV, ±39.062 mV, ±19.532 mV
Fault and Overvoltage
protection
±35 VDC (power off); +30 VDC, -25 VDC
(power on)
Sampling Rate
12 samples/sec (all channels)
Resolution
16 bits
Accuracy
±0.1% FSR @ 25°C
±0.3% FSR @ -40 and 75°C
Input Impedance
10M ohms
Installation
Connecting the Power
Connect the +12 to +36 VDC power line to the ioLogik E1200’s terminal
block V+ terminal; connect the ground from the power supply to the V-
terminal. Connect the ground pin ( ) if earth ground is available.
NOTE
For safety reasons, wires connecting the power supply should be
at least 2 mm in diameter (e.g., 12 gauge wires).