Moxa ioLogik E1240-T [4/5] Iologik e1242 specifications

Moxa ioLogik E1240 [4/5] Iologik e1242 specifications
Remote I/O
4
www.moxa.com
ioLogik E1242 Specifications
Inputs and Outputs
Digital Inputs: 4 channels
Configurable DIOs (by jumper): 4 channels
Analog Inputs: 4 channels
Isolation: 3k VDC or 2k Vrms
Digital Input
Sensor Type: Wet Contact (NPN or PNP), Dry Contact
I/O Mode: DI or Event Counter
Dry Contact:
• On: short to GND
• Off: open
Wet Contact (DI to COM):
• On: 10 to 30 VDC
• Off: 0 to 3 VDC
Common Type: 4 points per COM
Counter Frequency: 250 Hz
Digital Filtering Time Interval: Software Configurable
Digital Output
Type: Sink
I/O Mode: DO or Pulse Output
Pulse Output Frequency: 500 Hz
Over-Voltage Protection: 45 VDC
Over-Current Protection: 2.6 A (4 channels @ 650 mA)
Over-Temperature Shutdown: 175°C (typical), 150°C (min.)
Current Rating: 200 mA per channel
Analog Input
Type: Differential input
Resolution: 16 bits
I/O Mode: Voltage / Current (jumper selectable)
Input Range: 0 to 10 VDC, 0 to 20 mA, 4 to 20 mA, 4 to 20 mA
(burnout detection)
Accuracy:
±0.1% FSR @ 25°C
±0.3% FSR @ -10 and 60°C
±0.5% FSR @ -40 and 75°C
Sampling Rate:
• All channels: 12 samples/sec
• Per channel: 3 samples/sec
• Only one channel enabled: 12 samples/sec
Input Impedance: 10 mega-ohms (min.)
Built-in Resistor for Current Input: 120 ohms
Power Requirements
Input Voltage: 12 to 36 VDC
Input Current: 139 mA @ 24 VDC
MTBF (mean time between failures)
Time: 502,210 hrs
Standard: Telcordia SR332
ioLogik E1262 Specifications
Inputs and Outputs
Thermocouples: 8 channels
Isolation: 3k VDC or 2k Vrms
Thermocouple
Sensor Type: J (0 to 750°C), K (-200 to 1250°C), T (-200 to 350°C),
E (-200 to 900°C), R (-50 to 1600°C), S (-50 to 1760°C), B (600 to
1700°C), N (-200 to 1300°C)
Millivolt Type:
• Mode: ±78.126 mV, ±39.062 mV, ±19.532 mV
• Fault and over-voltage protection:
-35 to +35 VDC (power off)
-25 to +30 VDC (power on)
Sampling Rate:
• All channels: 12 samples/sec
• Per channel: 1.5 samples/sec
• Only one channel enabled: 12 samples/sec
Resolution: 16 bits
Accuracy:
±0.1% FSR @ 25°C
±0.3% FSR @ -40 and 75°C
Input Impedance: 10 mega-ohms
Power Requirements
Input Voltage: 12 to 36 VDC
Input Current: 118 mA @ 24 VDC
MTBF (mean time between failures)
Time: 631,418 hrs
Standard: Telcordia SR332
ioLogik E1260 Specifications
Inputs and Outputs
RTDs: 6 channels
Isolation: 3k VDC or 2k Vrms
RTD
Sensor Type:
• PT50, PT100, PT200, PT500 (-200 to 850°C)
• PT1000 (-200 to 350°C)
• Resistance of 310, 620, 1250, and 2200 ohms
Input Connection: 2- or 3-wire
Sampling Rate:
• All channels: 12 samples/sec
• Per channel: 2 samples/sec
• Only one channel enabled: 12 samples/sec
Resolution: 0.1°C or 0.1 ohm
Accuracy:
±0.1% FSR @ 25°C
±0.3% FSR @ -40 and 75°C
Input Impedance: 625 kilo-ohms
Power Requirements
Input Voltage: 12 to 36 VDC
Input Current: 110 mA @ 24 VDC
MTBF (mean time between failures)
Time: 660,260 hrs
Standard: Telcordia SR332
Power Requirements
Input Voltage: 12 to 36 VDC
Input Current: 194 mA @ 24 VDC
MTBF (mean time between failures)
Time: 888,656 hrs
Standard: Telcordia SR332
Скачать