Moxa ioLogik R1210 [4/6] Power and networking

Moxa ioLogik R1212 [4/6] Power and networking
- 4 -
Analog Output
Resolution
12 bits
Output Range
0 to 10 VDC, 4 to 20 mA
Voltage Output
10 mA (Max.)
Accuracy ±0.1% FSR @ 25°C
±0.3% FSR @ -40 and 75°C
Load Resistor
• Internal power: 400 ohms
• External 24V power: 1000 ohms
Installation
Power and Networking
Connect the +12 to +48 VDC power line to the ioLogik R1200’s terminal
block V+ terminal; connect the ground from the power supply to the V-
terminal. Connect the ground pin ( ) if earth ground is available.
NOTE
For safety reasons, the wires attached to the power should be at
least 2 mm (12 gauge) in diameter.
Switch Settings
The R1200 series provides Dual/Rep and Run/Initial switch settings to set
up the communication mode.
Duel (Default)
Dual RS-485 mode
Rep
Repeater mode
Run
User define communication parameters
Initial (Default)
Initial RS-485 communication parameters