Moxa ioLogik R1212 [23/64] Initial setup by usb

Moxa ioLogik R1212-T [23/64] Initial setup by usb
ioLogik R1200 Series Initial Setup
2-9
Initial Setup by USB
When setting up your ioLogik R1200 for the first time, you need to import the initial configuration and firmware
files onto a USB drive. But before you connect the USB drive to the ioLogik R1200’s USB port to install and
upgrade configurations and firmware, you first need to place the configuration files under a designated folder.
NOTE
The USB format should be FAT or FAT32.
The NTFS format is not supported.
Import Configuration File
To import configuration files via USB, follow these steps:
1. Create a new “config” folder on the USB drive
2. Use the ioSearch utility to export the configuration file from the device and place the file into the“config”
folder created in step 1 (above):
X\config\R12YY.txt
(X represents the USB drive, and R12YY represents the model type)
Upgrade Firmware
To upgrade the firmware by USB, follow these steps:
1. Create a new "fwr" folder on the USB drive.
2. Place the firmware file under the folder created in step1:
X\fwr\R12YY.1kp
(X represents the USB drive, and R12YY represent the model type)
Configure the Device
After you set up the USB drive, follow the steps below to configure your ioLogik R1200 device.
1. Power off the ioLogik R1200.
2. Set the DIP switch to “Initial” mode.
3. Plug the USB drive into the ioLogik R1200 device.
4. Power on the ioLogik R1200 and the USB drive will automatically install the system files.
(Process: Rdy LED Red blinking 3s, then Green blinking,
Result: RdyLED Green: pass, Rdy Red: Failed)
5. Power off the ioLogik R1200 device.
6. Unplug the USB drive.
7. Set the DIP switch to “Run” mode.

Содержание