Moxa ioLogik R1241 Руководство по аппаратной части онлайн [3/6] 171467

Moxa ioLogik R1212-T Руководство по аппаратной части онлайн [3/6] 171462
- 3 -
Communication Parameters (Initial mode)
Parity
None, Even, Odd (default = None)
Data Bits
8
Stop Bits
1, 2 (default = 1)
Flow Control
None, XON/XOFF (default = None)
Baudrate
1200 to 921.6 kbps (default = 9600)
Digital Input
Sensor Type
NPN, PNP, and Dry contact
I/O Mode
DI or Event Counter
Dry Contact
On: short to GND
Off: open
Wet Contact
(DI to COM)
On: 10 to 30 VDC
Off: 0 to 3 VDC
Isolation
3K VDC or 2K Vrms
Counter/Frequency
2.5 kHz, power off storage
Digital Output
I/O Mode
DO or Pulse Output
Pulse Wave
Width/Frequency
0.1 ms / 5 kHz
Over-voltage
Protection
45 VDC
Over-current
Protection
2.6 A (4 channels @ 650 mA)
Over-temperature
Shutdown
175°C (typical), 150°C (min.)
Current Rating
200 mA per channel
Isolation
3K VDC or 2K Vrms
Relay Output
Type
Form A (N.O.) relay outputs, 5A
Contact Rating
5 A @ 30 VDC, 5 A @ 250 VAC, 5 A @ 110 VAC
Inductance Load
2 A
Resistance Load
5 A
Breakdown Voltage
500 VAC
Relay On/Off Time
1500 ms (Max.)
Initial Insulation
Resistance
1G min. @ 500 VDC
Expected Life
100,000 times (Typical)
Initial Contact
Resistance
30 milli-ohms (Max.)
Pulse Output
0.3 Hz at rated load
Analog Input
Type
Differential input
Resolution
16 bits
I/O Mode
Voltage / Current
Input Range
0 to 10 VDC, 4 to 20 mA
Accuracy ±0.1% FSR @ 25°C
±0.3% FSR @ -10 and 60°C
±0.5% FSR @ -40 and 75°C
Sampling Rate (all
channels)
12 samples/sec
Input Impedance
10M ohms (minimum)
Built-in Resistor for
Current Input
120 ohms