Moxa ioLogik E2214-T [3/5] Analog output

Moxa ioLogik E2260 [3/5] Analog output
Remote I/O
3
www.moxa.com
ioLogik E2214 Specifications
ioLogik E2240 Specifications
Inputs and Outputs
Digital Inputs: 6 channels
Relay Outputs: 6 channels
Isolation: 3k VDC or 2k Vrms
Digital Input
Sensor Type: Wet Contact (NPN or PNP) and Dry Contact
I/O Mode: DI or Event Counter
Dry Contact:
• On: short to GND
• Off: open
Wet Contact (DI to GND):
• On: 0 to 3 VDC
• Off: 10 to 30 VDC
Common Type: 3 points per COM
Counter Frequency: 900 Hz
Digital Filtering Time Interval: Software Configurable
Relay Output
Type: Form A (N.O.) power relay
Inputs and Outputs
Analog Inputs: 8 channels
Analog Outputs: 2 channels
Analog Input
Isolation: 3k VDC or 2k Vrms
Type: Differential input
Resolution: 16 bits
I/O Mode: Voltage/Current (software selectable)
Input Range: ±150 mV, ±500 mV, ±5 V, ±10 V, 0 to 20 mA, 4 to 20 mA
Accuracy:
±0.1% FSR @ 25°C
±0.3% FSR @ -10 and 60°C
±0.5% FSR @ -40 and 75°C
Sampling Rate:
All channels:
• 10 samples/sec for voltage
• 6 samples/sec for current
Per channel:
• 1.25 samples/sec for voltage
• 0.75 samples/sec for current
Contact Current Rating:
• Inductive Load: 2 A @ 30 VDC, 250 VAC, 110 VAC
• Resistive Load: 5 A @ 30 VDC, 250 VAC, 110 VAC
Minimum permitted load: 1 A @ 5 VDC
Initial Insulation Resistance: 1000 mega-ohms (min.) @ 500 VDC
Mechanical Endurance: 1,000,000 operations
Electrical Endurance: 100,000 operations @ 5 A resistive load
Contact Resistance: 100 milli-ohms (max.)
Pulse Output: 0.3 Hz at rated load
Note: Ambient humidity must be non-condensing and remain between 5 and
95%. The relays of the ioLogik E2214 may malfunction when operating in high
condensation environments below 0° Celsius.
Power Requirements
Input Voltage: 12 to 36 VDC
Input Current: 170 mA @ 24 VDC
MTBF (mean time between failures)
Time: 307,239 hrs
Database: Telcordia SR332
Single channel:
• 1.25 samples/sec for voltage
• 0.75 samples/sec for current
Input Impedance: 900 kilo-ohms ohms (min.)
Built-in Resistor for Current Input: 120 ohms
Analog Output
Resolution: 12 bits
Output Range: 0 to 10 V, 4 to 20 mA
Drive Voltage: 15 VDC for current output
Accuracy:
±0.1% FSR @ 25°C
±0.3% FSR @ -10 and 60°C
±0.5% FSR @ -40 and 75°C
Load Resistor: Less than 250 ohms
Power Requirements
Input Voltage: 12 to 36 VDC
Input Current: 190 mA @ 24 VDC
MTBF (mean time between failures)
Time: 155,941 hrs
Standard: Telcordia SR332
ioLogik E2242 Specifications
Inputs and Outputs
Configurable DIOs (by software): 12 channels
Analog Inputs: 4 channels
Isolation: 3k VDC or 2k Vrms
Digital Input
Sensor Type: Wet Contact (NPN or PNP) and Dry Contact
I/O Mode: DI or Event Counter
Dry Contact:
• On: short to GND
• Off: Open
Wet Contact (DI to GND):
• On: 0 to 3 VDC
• Off: 10 to 30 VDC
Common Type: 6 points per COM
Isolation: 3k VDC or 2k Vrms
Counter Frequency: 900 Hz
Digital Filtering Time Interval: Software selectable
Digital Output
Type: Sink
I/O Mode: DO or Pulse Output
Pulse Output Frequency: 1 kHz
Over-Voltage Protection: 45 VDC
Over-Current Protection: 2.6 A (4 channels @ 650 mA)
Over-Temperature Shutdown: 175°C (min.)
Current Rating: 200 mA per channel
Analog Input
Type: Differential input
Resolution: 16 bits
I/O Mode: Voltage / Current (software selectable)
Input Range: ±150 mV, 0 to 150 mV, ±500 mV, 0 to 500 mV, ±5 V, 0
to 5 V, ±10 V, 0 to 10 V, 0 to 20 mA, 4 to 20 mA
Скачать