Thermozone Portier
15
General recommendations
Carefully read this instruction manual before
installation and use of the Thermozone Portier
(PS) unit . Keep these instructions in a safe place
for future reference.
Application area
The Thermozone Portier air curtains are intended
for stationary/permanent installation above
entrances and smaller doors with a height up to 2.5
meter.Protection class: IP21
Operation
The air is drawn in at the top of the unit and blown
out at high velocity across the doorway, providing a
protective air shield. The air shield minimises cold
draughts and reduces heat loss through open
doorways. For best efficiency, the air curtain(s)
should cover the whole width of the opening.
Mounting
The units may only be installed horizontally over a
doorway with the air-stream directed downwards.
For the protection of wider doorways, several units
can be mounted next to each other. For optimal
performance it is recommended that a minimum
gap of 80mm is maintained above the air-curtain.
The total distance between PS and the wall, and
to the ceiling must be at least 120mm. See fig. B.
The PS is mounted using the four pcs of threaded
M6 holes on top of the unit.
The PS can be suspended using wires/chains
connected to the lifting loops included. See fig. A.
It´s also possible to use threaded bars (M6)
connected directly to the threaded holes on top of
the unit. See fig C.
Electrical installation
The air-curtain(s) should only be wired by a
competent electrician, and in accordance with the
latest edition of IEE wiring regulations.
Different combinations of fan speed and heat
output are available. See wiring diagrams fig. H -
L.
To open the PS unit, loosen the 5 screws
positioned cloesest to the inlet grille and remove
the front by lifting it straight out/downwards. See
fig F..
On top of the unit there are knockouts (2xØ23mm,
2xØ29mm) for routing of electrical supply and
remote switching cables.
The cable-glands used must guarantee the
Assembly and operating instructions
protection class requirements!
Typ Output Voltage Min. cable area
kW V m m
2
All control 230V~ 0.75
PS210E03**3 230V~ / 400V 3N~ 2.5 / 1.5
PS210E06* 6 230V 3~ / 400V 3N~ 2.5 / 1.5
PS210E09* 9 230V 3~ / 400V 3N~ 6 / 2.5
PS215E09* 9 230V 3~ / 400V 3N~ 6 / 2.5
PS215E14*13.5 230V 3~ / 400V 3N~ 10 / 4
PS210A 0 230V~ 0.75
PS215A 0 230V~ 0.75
*Commutable units can be used for 3x230V
or
3x400V.
**Commutable units can be used for 230V
or
3x400V.
To convert the elements for PS210E06-9 and
PS215E09-14 see wiring diagram fig. R.
No converion has to be done for PS210E03.
The convert sockets are located behind the left end
cap and are easily accessible after taking off the
front panel
The power and voltage could be supplied in
different connection areas (see wiring diagram fig.
M - Q). In the distribution board it is to be indicated
that ”the air curtains can be supplied from more
than one connection”.
Adjusting the unit and the airflow
Direction and speed of the airflow should be
adjusted according to the load on the door.
Outside pressure forces the air stream to bend
towards the interior of the room (when the room is
heated and the outside is cold). To reduce this
effect, the airflow should be directed outwards. The
air director/grille is adjustable and should be
angled outwards (5°-10°) to achieve the best
protection of the door. The more load caused by
negative pressure differential, temperature
differences and wind, the more should the airflow
be directed outwards. The airflow can be adjusted
by use of the control box (CB22 or CB20).