Daikin FDQ125C_RZQG125L9V [12/52] Mounting the outdoor unit

Daikin FBQ125D_RZQSG125L9V [12/52] Mounting the outdoor unit
6Installation
Installerreferenceguide
12
RZQG71~140L_V1+Y1+RZQSG100~140L_V1+Y1
Splitsystemairconditioners
4P3855221–2014.08
6.3 Mountingtheoutdoorunit
6.3.1 Aboutmountingtheoutdoorunit
Typicalworkflow
Mountingtheoutdoorunittypicallyconsistsofthefollowingstages:
1 Providingtheinstallationstructure.
2 Installingtheoutdoorunit.
3 Providingdrainage.
4 Preventingtheoutdoorunitfromfallingover.
5 Protectingtheunitagainstsnowandwindbyinstallingasnow
cover and baffle plates. See "Preparing installation site" in
"5Preparation"onpage7.
6.3.2 Precautionswhenmountingtheoutdoor
unit
INFORMATION
Also read the precautions and requirements in the
followingchapters:
Generalsafetyprecautions
Preparation
6.3.3 Toprovidetheinstallationstructure
Check the strength and level of the installation ground so that the
unitwillnotcauseanyoperatingvibrationornoise.
Fix the unit securely by means of foundation bolts in accordance
withthefoundationdrawing.
Prepare 4sets of anchorbolts, nuts andwashers (field supply)as
follows:
(mm)
>150
620
350
(345-355)
M12
a
a Makesurenottocoverthedrainholes.
INFORMATION
The recommended height of the upper protruding part of
theboltsis20mm.
20
NOTICE
Fixtheoutdoorunittothefoundationboltsusingnutswith
resin washers (a). If the coating on the fastening area is
strippedoff,thenutsrusteasily.
a
6.3.4 Toinstalltheoutdoorunit
M12
6.3.5 Toprovidedrainage
Makesurethatcondensationwatercanbeevacuatedproperly.
Install the unit on a base to make sure that there is a proper
drainageinordertoavoidiceaccumulation.
Prepareawaterdrainagechannelaroundthefoundationtodrain
wastewatersurroundingtheunit.
Avoid drain water flowing over the footpath, so that it does not
becomeslipperyincaseofambientfreezingtemperatures.
Ifyou install theunitona frame, installawaterproofplate within
150 mm of the underside of the unit in order to prevent the
invasionofwaterintheunitandtoavoidthedrainwaterdripping
(seethefollowingillustration).
INFORMATION
Ifnecessary,youcanuseadrainplugkit(fieldsupply)to
preventdrainwaterfromdripping.
NOTICE
Ifdrainholesoftheoutdoorunitarecoveredbyamounting
base or by floor surface, raise the unit to provide a free
spaceofmorethan150mmundertheoutdoorunit.
≥150 mm