6Installation
Installerreferenceguide
21
RZQG71~140L_V1+Y1+RZQSG100~140L_V1+Y1
Splitsystemairconditioners
4P3855221–2014.08
6.7.2 Aboutelectricalcompliance
RZQ(S)G_V1+RZQSG100+125_Y1
Equipment complying with EN/IEC 61000312 (European/
International Technical Standard setting the limits for harmonic
currents produced by equipment connected to public lowvoltage
systemswithinputcurrent>16Aand≤75Aperphase.).
RZQG100~140_Y1+RZQSG140_Y1
Equipmentcomplyingwith:
EN/IEC 61000312 provided that the shortcircuit power S
sc
is
greater than or equal to the minimum S
sc
value at the interface
pointbetweentheuser'ssupplyandthepublicsystem.
EN/IEC 61000312 = European/International Technical
Standard setting the limits for harmonic currents produced by
equipment connected to public lowvoltage systems with input
current>16Aand≤75Aperphase.
Itistheresponsibilityoftheinstalleroruseroftheequipmentto
ensure,byconsultationwiththedistributionnetworkoperatorif
necessary, that the equipment is connected only to a supply
with a shortcircuit power S
sc
greater than or equal to the
minimumS
sc
value.
Model MinimumS
sc
value
RZQG100~140_Y1+RZQSG140_Y1 1170kVA
(a)
(a) Thisisthemoststringentvalue.Forspecificproductdata,
seethedatabooks.
6.7.3 Precautionswhenconnectingthe
electricalwiring
INFORMATION
Also read the precautions and requirements in the
followingchapters:
Generalsafetyprecautions
Preparation
DANGER:RISKOFELECTROCUTION
INFORMATION
Moreinformationabout thelegendandthelocationofthe
wiring diagram of the unit can be found in "12.5 Wiring
diagram"onpage35.
WARNING
ALWAYSusemulticorecableforpowersupplycables.
CAUTION
For use of units in applications with temperature alarm
settings it is recommended to foresee a delay of 10
minutes for signalling the alarm in case the alarm
temperature is exceeded. The unit may stop for several
minutesduringnormaloperationfor"defrostingtheunit",or
whenin"thermostatstop"operation.
6.7.4 Guidelineswhenconnectingtheelectrical
wiring
Keepthefollowinginmind:
Ifstrandedconductorwiresarebeingused,installaroundcrimp
style terminal on the tip. Place the round crimpstyle terminal on
the wire up to the covered part and fasten the terminal with the
appropriatetool.
b a
a Strandedconductorwire
b Roundcrimpstyleterminal
Usethefollowingmethodsforinstallingwires:
Wiretype Installationmethod
Singlecorewire
cb
c
aa
A
AA´
aCurledsinglecorewire
bScrew
cFlatwasher
Strandedconductor
wirewithround
crimpstyleterminal
c b ba c
a
B
B
aTerminal
bScrew
cFlatwasher
NOTICE
Precautionswhenlayingpowerwiring:
Do not connect wiring of different thicknesses to the
power terminal block (slack in the power wiring may
causeabnormalheat).
When connecting wiring which is the same thickness,
doasshowninthefigurebelow.
Forwiring,usethedesignatedpowerwireandconnect
firmly, then secure to prevent outside pressure being
exertedontheterminalboard.
Use an appropriate screwdriver for tightening the
terminal screws. A screwdriver with a small head will
damage the head and make proper tightening
impossible.
Overtighteningtheterminalscrewsmaybreakthem.
Tighteningtorques
Item Tighteningtorque(N•m)
M4(X1M) 1.2~1.8
M4(earth) 1.2~1.4
M5(X1M) 2.0~3.0
M5(earth) 2.4~2.9