8
N
OTE
:
S
ETTINGS ARE MADE THROUGH SUPPLIED
P
OWER
C
HUTE SOFTWARE OR OPTIONAL
S
MART
S
LOT
ACCESSORY CARDS
.
F
UNCTION
F
ACTORY
D
EFAULT
U
SER
S
ELECTABLE
C
HOICES
D
ESCRIPTION
Low Battery Warning.
PowerChute interface
software provides
automatic, unattended
shutdown when
approximately two minutes
(by default) of battery
operated run time remains.
Brightly lit: Low battery
warning interval is about
two minutes.
Dimly lit: Low battery
warning interval is about
five minutes.
Off: Low battery warning
interval is about eight
minutes.
Possible interval settings:
5, 7, 10, 12, 15,
18 minutes.
The low battery warning
beeps are continuous when
two minutes of run time
remain.
You can change the warning
interval default setting
through PowerChute
software.
Synchronized Turn-on
Delay
0 seconds 20, 60, 120, 240, 480,
720, 960 seconds
The UPS will wait the
specified time after the return
of utility power before turn on
to avoid branch circuit
overload.
High Transfer Point 100 V:
108 VAC
120 V:
127VAC
230 V:
253 VAC
100 V:
110, 112, 114 Vac
120 V:
130, 133, 136 Vac
230 V:
257, 261, 265 Vac
To avoid unnecessary battery
usage, set the high transfer
point higher if the utility
voltage is chronically high
and the connected equipment
is known to work under this
condition.
Low Transfer Point 100 V:
92 Vac
120 V:
106 Vac
230 V:
208 Vac
100 V:
86, 88, 90 Vac
120 V:
97, 100, 103 Vac
230 V:
196, 200, 204 Vac
Set the low transfer point
lower if the utility voltage is
chronically low and the
connected equipment can
tolerate this condition.