APC Smart-UPS SUA750RMI2U [10/19] Onfigurable

APC Smart-UPS SUA750RMI2U [10/19] Onfigurable
7
3: USER CONFIGURABLE ITEMS
N
OTE
:
S
ETTINGS ARE MADE THROUGH SUPPLIED
P
OWER
C
HUTE SOFTWARE OR OPTIONAL
S
MART
S
LOT
ACCESSORY CARDS
.
F
UNCTION
F
ACTORY
D
EFAULT
U
SER
S
ELECTABLE
C
HOICES
D
ESCRIPTION
Automatic Self-Test Every 14 days
(336 hours)
Every 7 days
(168 hours),
On Startup Only,
No Self-Test
This function sets the interval
at which the UPS will execute
a self-test. Refer to your
software manual for details.
UPS ID UPS_IDEN Up to eight characters to
define the UPS
Use this field to uniquely
identify the UPS, (i.e. server
name or location) for network
management purposes.
Date of Last Battery
Replacement
Manufacture
Date
Date of Battery
Replacement
mm/dd/yy
Reset this date when you
replace the battery module.
Minimum Capacity Before
Return from Shutdown
0 percent 15, 25, 35, 50, 60, 75,
90 percent
The UPS will charge its bat-
teries to the specified
percentage before return from
a shutdown.
Voltage Sensitivity
The UPS detects and reacts
to line voltage distortions
by transferring to battery
operation to protect the
connected equipment.
Where power quality is
poor, the UPS may
frequently transfer to
battery operation. If the
connected equipment can
operate normally under
such conditions, reduce the
sensitivity setting to
conserve battery capacity
and service life.
Brightly lit: UPS is set to
high sensitivity.
Dimly lit: UPS is set to
medium sensitivity.
Off: UPS is set to low
sensitivity.
To change the UPS
sensitivity, press the voltage
sensitivity button (rear
panel). Use a pointed object
(such as a pen) to do so.
You can change the
sensitivity level through
PowerChute software.
Alarm Delay After Line
Fail
5 second delay 30 second delay, At Low
Battery Condition, No
To avoid alarms for minor
power glitches, set the alarm
delay.
Shutdown Delay 20 seconds 0, 60, 120, 240, 480, 720,
960 seconds
Sets the interval between the
time when the UPS receives a
shutdown command and
actual shutdown.