54
Duct type air conditioners
series: Roka II
After  nishing drainpipe installation, pour some water into the water receiver plate to check if
the water  ows smoothly.
1) Poke the Water Level Switch, remove the cover, use water pipe to pour 2000 ml water into the
water receipt plate through the water inlet.
2) Turn on the power to Cooling operation. Check the pump s operation and switch on the Wa-
ter Level Switch. Check the pump s sound and look into the transparent hard pipe in the outlet
at the same time to check if the water can discharge normally.
3) Stop the air conditioner running, turn o the power, and put back the cover. After 3 minutes,
check if it has abnormity. If the collocation of drainpipes is illogical, the water will  ow back
overfull, which will cause the alarm lamp  ashes, even over ow from the water receipt plate.
7.4. Electric wiring
See the table 7.4.1. for cross-section areas of wires and lines.
If the power cable is too long, please choose cable with larger cross-section area to guarantee
normal power supply.
Table 7.4.1.
Model KC-Roka II-18M KC-Roka II-24M
Power supply ph/V/Hz 1/220-240/50
Min/max voltage V 198/254 198/254
Outdoor unit power wiring n×mm
2
3×2.5 3×2.5
Indoor unit power wiring n×mm
2
3×2.5 3×2.5
Signal wiring n×mm
2
3×1.5+2×0.75 3×0.75+2×0.75
Table 7.4.1.
Model KC-Roka II-36M KC-Roka II-48M KC-Roka II-60M
Power supply ph/V/Hz
1/220-240/50 (Indoor unit)
3/380/50 (Outdoor unit)
Min/max voltage V
198/254 (Indoor unit)
342/418 (Outdoor unit)
Outdoor unit power
wiring
n×mm
2
5×2.5 5×2.5 5×2.5
Indoor unit power
wiring
n×mm
2
3×2.5 3×2.5 3×2.5
Signal wiring n×mm
2
4×0.75+2×0.75 4×0.75+2×0.75 4×0.75+2×0.75