5. Drainage piping work
5.1. Drainage Piping Work (Fig. 5-1)
• Install the drain pipe so that it slopes downward (1/100 or more).
• Use VP20 (O.D. ø26 PVC TUBE) for the drain pipes.
• The drain hose can be cut with a knife to match on-site requirements.
• When connecting to the VP20, use the accessory drain socket
b. Securely fasten
the socket to the pipe with vinyl chloride type adhesive so that it doesn’t leak.
• Do not insert the drain pipe directly into a location where sulfur-containing gas is
likely to be generated (i.e. a sewer).
• Make sure that no water leaks from the drain pipe joint.
• If the drain pipe passes through an indoor area, wrap commercially available insula
-
tion (polyethylene foam of specific gravity 0.03 with a thickness of 9 mm or more)
around it and cover the surface with tape. This will prevent air from entering and
condensation from forming.
5.2. Drainage check (Fig. 5-2)
• After installing the pipes, make sure that the waste water is being drained out
properly and that water is not leaking from the joints (also perform these checks if
installation is done during the heating season).
• Insert a water supply pump from the right side of the air outflow port and pump
about 1L of water into the unit.
* Pump gently, toward the heat exchanger side plate or the unit inside wall.
* Always pump from the right side of the air outflow port.
* If the unit has a heater, the heater will be attached to the front surface of the heat
exchanger, make sure that water does not get onto the heater.
c
a
b
d
e
Fig. 5-1
a Drain hose
b Drain socket
c Drain pipe VP20 (obtain locally)
Fig. 5-2
a Heat exchanger
b Side plate
c Water
d Inside wall
e Drain pan
4. Installing the refrigerant piping
g
c
d
b
f
e
c
a
Fig. 4-4
Fig. 4-5
a Liquid pipe
b Gas pipe
c Frame
d Square hole
e Pass the band through the square hole in the
frame to hold the refrigerant pipes in place.
1 Gas pipe insulation
2 Liquid pipe insulation
3 Band
Refrigerant piping connection (Fig. 4-4)
1. Remove the screw from the air intake grill handle and then remove the air intake
grill by pulling it up and forward.
2. Remove the tapping screw that holds the pipe support in place and then remove
the pipe support.
3. Remove the cushions.
• Be sure to remove the three cushions from the fan before operating the indoor
unit.
• After finishing this work, always reassemble the unit.
• When reassembling, hook the air intake grill hangers
c onto the holes in the sides
of the panels.
a Air intake grill
b Pipe support
c Hanger
d Side panel
e Screw
f 4 × 10 tapping screw
g Cushion
Insulate flare joints 1 and 2 of the gas and refrigerant pipes completely. If any part
of the joints are exposed, condensation can drip down. (Fig. 4-5)
• Fasten the gas pipe insulation
1 and the liquid pipe insulation 2 at both ends so
that they will not slip and align with one another.
• After the insulation is installed, use a band
3 to fasten the refrigerant pipe to the
frame (below the pipe joint section). This will prevent the refrigerant pipe from lifting
up off of the frame.
(When the refrigerant pipe is off of the frame, the grille cannot be installed.)
• After connecting the refrigerant piping to the indoor unit, be sure to test the pipe
connections for gas leakage with nitrogen gas. (Check that there is no refrigerant
leakage from the refrigerant piping to the indoor unit.)
Conduct the airtightness test before connecting the outdoor unit stop valve and the
refrigerant pipe.
If the test is conducted after the valve and pipe are connected, gas, which is used
for checking the airtightness, will leak from the stop valve and flow into the outdoor
unit, resulting in abnormal operation.
Содержание
- Air conditioners 1
- Deutsch 1
- English 1
- Español 1
- Eγxeipiδio oδhγiωn eγkataσtaσhσ 1
- Eλληνικά 1
- Français 1
- Installatiehandleiding 1
- Installation manual 1
- Installationshandbuch 1
- Installationsmanual 1
- Italiano 1
- Manual de instalación 1
- Manual de instalação 1
- Manuale di installazione 1
- Manuel d installation 1
- Montaj elki tabi 1
- Nederlands 1
- Português 1
- Psa rp ka 1
- Svenska 1
- Türkçe 1
- Before electric work 2
- Before installation euvironment 2
- Before installation or relocation 2
- Before starting the test run 2
- Contents 2
- Safety precautions 2
- Check the indoor unit accessories 3
- Fig 2 1 3
- Fig 3 1 3
- Fig 3 2 3
- Installation location 3
- Installing the indoor unit 3
- Outline dimensions indoor unit fig 2 1 3
- Tip over prevention bracket fig 3 2 3
- Fig 3 3 4
- Fig 3 4 4
- Floor mounting 4
- For devices that use r410a refrigerant 4
- Installing the indoor unit 4
- Installing the refrigerant piping 4
- Mounting the tip over prevention bracket fig 3 3 4
- Precautions 4
- Fig 4 1 5
- Fig 4 2 5
- Fig 4 3 5
- Indoor unit fig 4 1 5
- Installing the refrigerant piping 5
- Refrigerant and drainage pipe locations fig 4 3 5
- Drainage check fig 5 2 6
- Drainage piping work 6
- Drainage piping work fig 5 1 6
- Fig 4 4 6
- Fig 4 5 6
- Fig 5 1 6
- Fig 5 2 6
- Installing the refrigerant piping 6
- 1 system 7
- Electric wiring fig 6 1 7
- Electrical work 7
- Fig 6 1 7
- Indoor unit power supplied from outdoor unit 7
- Simultaneous twin triple four system 7
- 1 system 8
- Affix a label b that is included with the manuals near each wiring diagram for the indoor and outdoor units 8
- Electrical work 8
- If the indoor and outdoor units have separate power supplies refer to the table at the below if the optional wiring replacement kit is used change the indoor unit electrical box wiring refering to the figure in the right and the dip switch settings of the outdoor unit control board 8
- Indoor unit specifications indoor power supply terminal kit option required indoor unit electrical box connector con nection change required 8
- Label affixed near each wiring diagram for the indoor and outdoor units required 8
- Notes 1 wiring size must comply with the applicable local and national code 2 power supply cords and indoor unit outdoor unit connecting cords shall not be lighter than polychloroprene sheathed flexible cord design 60245 iec 57 3 install an earth longer than other cables 8
- On off 1 2 sw8 3 8
- Outdoor unit dip switch settings when using separate indoor unit outdoor unit power supplies only 8
- Separate indoor unit outdoor unit power supplies for puhz application only 8
- Simultaneous twin triple four system 8
- The following connection patterns are available the outdoor unit power supply patterns vary on models 8
- The optional wiring replacement kit is required 8
- The optional wiring replacement kits are required 8
- There are three types of labels labels a b and c affix the appropriate labels to the units according to the wiring method 8
- Electrical work 9
- Fig 6 2 9
- Function setting on the remote controller 9
- Function setting on the unit fig 6 2 9
- Function settings 9
- Before test run 10
- Fig 7 1 10
- Fig 7 2 10
- Self check fig 7 2 10
- Test run 10
- Test run 11
- 1 press the button for three seconds to activate the maintenance mode 12
- 2 press the temp buttons to set the refrigerant address 12
- 3 select the data you want to display 12
- 4 press the button 12
- 5 the data is displayed in 12
- 6 press the button for three seconds or press the button to deactivate the maintenance mode 12
- By using the maintenance mode you can display many types of maintenance data on the remote controller such as the heat exchanger temperature and compressor current consumption for the indoor and outdoor units this function can be used whether the air conditioner is operating or not during air conditioner operation data can be checked during either normal operation or maintenance mode stable operation this function cannot be used during the test run the availability of this function depends on the connecting outdoor unit refer to the brochures 12
- Display example comp discharge temperature 64 c 12
- Easy maintenance function 12
- Maintenance mode operation procedures 12
- Press the button 12
- Press the button to select the operation mode 12
- Repeat steps 2 to 5 to check another date 12
- Stable operation using the maintenance mode the operation frequency can be fixed and the operation can be stabilized if the air conditioner is stopped use the following procedure to start this operation 12
- The filter operation time displayed is the number of hours the filter has been used since the filter reset was performed 12
- You can check the data using steps 3 to 5 of the maintenance mode operation procedures while waiting for the stable operation 12
- Дренажные трубы 27 6 электрические работы 28 7 выполнение испытания 31 8 функция простого техобслуживания 33 13
- Меры предосторожности 13
- Меры предосторожности 23 2 место установки 24 3 установка внутреннего прибора 24 4 прокладка труб хладагента 25 13
- Перед тестовым прогоном 13
- Перед установкой или перемещением 13
- Перед установкой окружающая среда 13
- Перед электрическими работами 13
- Содержание 13
- Fig 2 1 14
- Fig 3 1 3 крепежный кронштейн для предотвращения опрокидывания прибора fig 3 2 14
- Fig 3 2 14
- Контурные габариты внутренний прибор fig 2 1 14
- Место установки 14
- Проверьте наличие дополнительных принадлежностей к внутреннему прибору 14
- Установка внутреннего прибора 14
- Fig 3 3 15
- Fig 3 4 15
- Для устройств в которых используется хладагент r410a 15
- Меры предосторожности 15
- Монтаж крепежного кронштейна для предотвращения опрокидывания прибора fig 3 3 15
- Монтаж на полу 15
- Прокладка труб хладагента 15
- Установка внутреннего прибора 15
- Fig 4 1 16
- Fig 4 2 16
- Fig 4 3 16
- Внутренний прибор fig 4 1 16
- Прокладка труб хладагента 16
- Расположение труб хладагента и дренажных труб fig 4 3 16
- Fig 4 4 17
- Fig 4 5 17
- Fig 5 1 17
- Fig 5 2 17
- Дренажные трубы 17
- Проверка дренажа fig 5 2 17
- Прокладка дренажных труб fig 5 1 17
- Прокладка труб хладагента 17
- Fig 6 1 18
- Одновременная двойная тройная четверная система 18
- Питание на внутренний прибор подается от наружного прибора 18
- Система 1 1 18
- Электрические работы 18
- Электрические работы fig 6 1 18
- On off 1 2 sw8 3 19
- Одновременная двойная тройная четверная система 19
- Отдельные источники электропитания для внутреннего прибора наружного прибора только для применения puhz 19
- Система 1 1 19
- Электрические работы 19
- Fig 6 2 20
- Установки функций 20
- Функциональная настройка на пульте дистанционного управления 20
- Функциональная настройка прибора fig 6 2 20
- Электрические работы 20
- Fig 7 1 21
- Fig 7 2 21
- Выполнение испытания 21
- Перед пробным прогоном 21
- Самодиагностика fig 7 2 21
- Выполнение испытания 22
- Процедуры работы в режиме техобслуживания 23
- Функция простого техобслуживания 23
Похожие устройства
- Mitsubishi Electric PLA-RP71BA / PUHZ-SHW80VHA Инструкция по эксплуатации
- Mitsubishi Electric PLA-RP71BA / PUHZ-SHW80VHA Руководство по установке
- Mitsubishi Electric PLA-RP71BA / PUHZ-SHW80VHA Сертификат
- Mitsubishi Electric PSA-RP125KA / PUHZ-ZRP125YKA Инструкция по эксплуатации
- Mitsubishi Electric PSA-RP125KA / PUHZ-ZRP125YKA Инструкция по установке
- Mitsubishi Electric PLA-RP140BA / PUHZ-ZRP140YKA Инструкция по эксплуатации
- Mitsubishi Electric PLA-RP140BA / PUHZ-ZRP140YKA Руководство по установке
- Mitsubishi Electric PLA-RP140BA / PUHZ-ZRP140YKA Сертификат
- EQTA BC10P Инструкция по эксплуатации
- Mitsubishi Electric PLA-RP100BA / PUHZ-ZRP100VKA Инструкция по эксплуатации
- Mitsubishi Electric PLA-RP100BA / PUHZ-ZRP100VKA Руководство по установке
- Mitsubishi Electric PLA-RP100BA / PUHZ-ZRP100VKA Сертификат
- EQTA BC05 Инструкция по эксплуатации
- Mitsubishi Electric PSA-RP71KA / SUZ-KA71VA Инструкция по эксплуатации
- Mitsubishi Electric PSA-RP71KA / SUZ-KA71VA Инструкция по установке
- Mitsubishi Electric PLA-RP125BA / PUHZ-ZRP125VKA Инструкция по эксплуатации
- Mitsubishi Electric PLA-RP125BA / PUHZ-ZRP125VKA Руководство по установке
- Mitsubishi Electric PLA-RP125BA / PUHZ-ZRP125VKA Сертификат
- Mitsubishi Electric PLA-RP125BA / PUHZ-SHW140YHA Инструкция по эксплуатации
- Mitsubishi Electric PLA-RP125BA / PUHZ-SHW140YHA Руководство по установке