7. Test run
Step 2 Switch the remote controller to “Test run”.
1
Select “Test run” from the Service menu, and press the [SELECT] button. (Fig. 7-1)
2
Select “Test run” from the Test run menu, and press the [SELECT] button. (Fig. 7-2)
3
The test run operation starts, and the Test run operation screen is displayed.
F1 F2 F3 F4
Cool
Pipe
Auto
Switch disp.
Mode Fan
RemainTest run
Fig. 7-3
F1 F2 F3 F4
unem ecivreS
rosruC
:unem niaM
Test run
Input maintenance info.
Function setting
Check
Self check
Fig. 7-1
F1 F2 F3 F4
Test run menu
Cursor
Service menu:
Test run
Drain pump test run
Fig. 7-2
F1 F2 F3 F4
Remain
Vane
Fig. 7-4
Step 3 Perform the test run and check the airfl ow temperature and auto vane.
1
Press the [F1] button to change the operation mode. (Fig. 7-3)
Cooling mode: Check that cool air blows from the unit.
Heating mode: Check that warm air blows from the unit.
2
Press the [SELECT] button to display the Vane operation screen, and then press
the [F1] and [F2] buttons to check the auto vane. (Fig. 7-4)
Press the [RETURN] button to return to the Test run operation screen.
Step 4 Confi rm the operation of the outdoor unit fan.
The speed of the outdoor unit fan is controlled in order to control the performance of the unit. Depending on the ambient air, the fan will rotate at a slow speed and will keep
rotating at that speed unless the performance is insuffi cient. Therefore, the outdoor wind may cause the fan to stop rotating or to rotate in the opposite direction, but this is
not a problem.
Step 5 Stop the test run.
1
Press the [ON/OFF] button to stop the test run. (The Test run menu will appear.)
Note: If an error is displayed on the remote controller, see the table below.
LCD Description of malfunction LCD Description of malfunction LCD Description of malfunction
P1 Intake sensor error P9 Pipe sensor error (dual-wall pipe)
E0 ~ E5
Communication error between the
remote controller and the indoor unit
P2 Pipe sensor error (liquid pipe) PA Leakage error (refrigerant system)
P4
Drain fl oat switch connector disconnected
(CN4F)
PL Refrigerant circuit abnormal
P5 Drain overfl ow protection operation FB Indoor controller board error
E6 ~ EF
Communication error between the
indoor unit and the outdoor unit
P6
Freezing/overheating protection
operation
U*, F*
(* indicates an
alphanumeric
character
excluding FB.)
Outdoor unit malfunction
Refer to the wiring diagram for the
outdoor unit.
P8 Pipe temperature error
See the table below for the details of the LED display (LED 1, 2, and 3) on the indoor controller board.
LED1 (microcomputer power supply) Indicates whether control power is supplied. Make sure that this LED is always lit.
LED2 (remote controller power supply)
Indicates whether power is supplied to the wired remote controller. The LED is lit only for the indoor unit that is con-
nected to the outdoor unit that has an address of 0.
LED3 (indoor/outdoor unit communication) Indicates whether the indoor and outdoor units are communicating. Make sure that this LED is always blinking.
7.2.2. Using SW4 in outdoor unit
Refer to the outdoor unit installation manual.
7.3. Self-check
■ Refer to the installation manual that comes with each remote controller for details.
Содержание
- Air conditioners кондиционеры 1
- Deutsch 1
- English 1
- Español 1
- Français 1
- Installatiehandleiding 1
- Installation manual 1
- Installationshandbuch 1
- Installationsmanual 1
- Italiano 1
- Manual de instalación 1
- Manual de instalação 1
- Manuale di installazione 1
- Manuel d installation 1
- Montaj elki tabi 1
- Nederlands 1
- Pla rp ba series pla zrp ba series 1
- Português 1
- Svenska 1
- Türkçe 1
- Εγχειριδιο οδηγιων εγκαταστασησ 1
- Ελληνικά 1
- Руководство по установке 1
- Русский 1
- Before electric work 2
- Before installation environment 2
- Before installation or relocation 2
- Before starting the test run 2
- Contents 2
- Note the phrase wired remote controller in this installation manual refers only to the par 31maa if you need any information for the other remote controller please refer to either the installation manual or initial setting manual which are included in these boxes 2
- Safety precautions 2
- Ceiling openings and suspension bolt installation locations fig 3 2 3
- Check the indoor unit accessories fig 3 1 3
- Fig 3 1 3
- Fig 3 2 3
- Fig 3 3 3
- Installation location 3
- Installing the indoor unit 3
- Refrigerant and drainage piping locations of indoor unit 3
- Branch duct hole and fresh air intake hole fig 3 4 4
- Confi rming the position of main unit and tightening the suspension bolts fig 3 8 4
- Fig 3 4 4
- Fig 3 5 4
- Fig 3 6 fig 3 7 4
- Fig 3 8 4
- Installing the indoor unit 4
- Suspension structure give site of suspension strong structure fig 3 5 4
- Unit suspension procedures fig 3 6 4
- Connecting pipes fig 4 1 5
- Fig 4 1 5
- Fig 4 2 5
- Installing the refrigerant piping 5
- Precautions 5
- Drainage piping work 6
- Drainage piping work fig 5 1 6
- Fig 4 3 6
- Fig 5 1 6
- Fig 5 2 6
- For twin triple combination 6
- Indoor unit fig 4 3 6
- Installing the refrigerant piping 6
- Electrical work 7
- Fig 6 1 7
- Indoor unit fig 6 1 7
- 1 system 8
- Electrical work 8
- On off 1 2 sw8 3 8
- Separate indoor unit outdoor unit power supplies for puhz application only 8
- Simultaneous twin triple quadruple system 8
- Electrical work 9
- Fig 6 2 9
- Fig 6 3 9
- Fig 6 4 9
- For wired remote controller 9
- For wireless remote controller 9
- Remote controller 9
- Electrical work 10
- Fig 6 5 fig 6 6 10
- Fig 6 7 fig 6 8 10
- Fig 6 9 10
- Function setting on the unit selecting the unit functions 10
- Function settings 10
- Electrical work 11
- Fig 6 10 11
- Function setting on the remote controller 11
- Electrical work 12
- Explanation of word refrigerant address no and unit no are the numbers given to each air conditioner outlet no is the number given to each outlet of air conditioner refer to the right up down air direction is the direction angle to fi x 12
- Fixed setting 12
- How to set the fi xed up down air direction only for wired remote controller and puhz pu h application 12
- Only the particular outlet can be fixed to certain direction with the procedures below once fi xed only the set outlet is fi xed every time air conditioner is turned on other outlets follow up down air direction setting of the remote controller 12
- Remote controller setting 12
- Before test run 13
- Electrical work 13
- Test run 13
- Using wired remote controller 13
- Fig 7 1 14
- Fig 7 2 14
- Fig 7 3 14
- Fig 7 4 14
- Self check 14
- Test run 14
- Using sw4 in outdoor unit 14
- Test run 15
- Check of drainage fig 7 5 16
- Fig 7 5 16
- System control 16
- Test run 16
- Checking the contents fig 9 1 17
- Fig 9 1 17
- Fig 9 2 17
- Fig 9 3 17
- Fig 9 4 17
- Fig 9 5 17
- Installing the grille 17
- Preparations fig 9 5 17
- Preparing to attach the grille fig 9 2 17
- Removing the corner panel fig 9 4 17
- Removing the intake grille fig 9 3 17
- Selection of the air outlets 17
- Fig 9 10 18
- Fig 9 6 18
- Fig 9 7 18
- Fig 9 8 18
- Fig 9 9 18
- Installation of i see sensor corner panel fig 9 10 18
- Installing the grille 18
- Installing the intake grille fig 9 9 18
- Securing the grille fig 9 7 18
- Temporary installation of the grille fig 9 6 18
- Wire connection fig 9 8 18
- Easy maintenance function 19
- Fig 9 11 19
- Installing the grille 19
- Locking the up down airfl ow direction fig 9 11 19
- Меры предосторожности 20
- Меры предосторожности 00 2 место установки 01 3 установка внутреннего прибора 01 4 прокладка труб хладагента 03 5 дренажные трубы 04 20
- Перед тестовым прогоном 20
- Перед установкой или перемещением 20
- Перед установкой окружающая среда 20
- Перед электрическими работами 20
- Содержание 20
- Электрические работы 05 7 выполнение испытания 211 8 управление системой 14 9 установка вентиляционной решетки 15 10 функция простого техобслуживания 17 20
- Fig 3 1 21
- Fig 3 2 21
- Fig 3 3 21
- Место установки 21
- Проверьте наличие дополнительных прина длежностей к внутреннему прибору fig 3 1 21
- Расположение отверстия в потолке и навесных болтов fig 3 2 21
- Расположение труб хладагента и дренажных труб для внутреннего блока 21
- Установка внутреннего прибора 21
- Fig 3 4 22
- Fig 3 5 22
- Fig 3 6 fig 3 7 22
- Fig 3 8 22
- Отверстие для ответвления вентиляционного канала и входное отверстие для свежего воздуха fig 3 4 22
- Подвесная конструкция обеспечьте прочность на месте подвешивания fig 3 5 22
- Порядок подвешивания прибора fig 3 6 22
- Проверка расположения главного прибора и затягивание навесных болтов fig 3 8 22
- Установка внутреннего прибора 22
- Fig 4 1 23
- Fig 4 2 23
- Меры предосторожности 23
- Прокладка труб хладагента 23
- Соединение труб fig 4 1 23
- Fig 4 3 24
- Fig 5 1 24
- Fig 5 2 24
- Внутренний прибор fig 4 3 24
- Для комбинации из двух трех элементов 24
- Дренажные трубы 24
- Дренажные трубы fig 5 1 24
- Прокладка труб хладагента 24
- Fig 6 1 25
- G g g g 25
- Внутренний прибор fig 6 1 25
- Электрические работы 25
- On off 1 2 sw8 3 26
- Если у внутреннего и наружного приборов различные источники электропитания см таблицу ниже при использовании комплекта клемм источника электропитания внутреннего прибора замените проводку распределительной коробки внутреннего прибора в соответствии с рисунком справа и измените настройки микропереключателя панели управления наружного прибора 26
- Изменение соединения разъема распределитель ной коробки внутреннего прибора 26
- Комплект клемм источника электропитания внутреннего прибора дополнительно 26
- Настройка микропереключателя наружного прибора только при использовании отдельных источников электропитания для внутреннего прибора наружного прибора 26
- Одновременная двойная тройная четверная система 26
- Система 1 1 26
- Электрические работы 26
- Fig 6 2 27
- Fig 6 3 27
- Fig 6 4 27
- Для беспроводного пульта дистанционного управления 27
- Для проводного пульта дистанционного управления 27
- Пульт дистанционного управления 27
- Электрические работы 27
- Fig 6 5 fig 6 6 28
- Fig 6 7 28
- Fig 6 8 28
- Fig 6 9 28
- Установки функций 28
- Функциональная настройка прибора выбор функций прибора 1 для проводного пульта дистанционного управления 28
- Электрические работы 28
- Fig 6 10 29
- Функциональная настройка на пульте дистанционного управления 29
- Электрические работы 29
- Порядок настройки фиксированного направленного вниз потока воздуха только для проводного пульта дистанционного управле ния и для применения puhz pu h 30
- Пояснение терминов охладителя и изделия это номера присваиваемые каж дому кондиционеру выпускного отверстия это номер каждого выпускного отверс тия кондиционера см рисунок справа направление воздуха вверх вниз это фиксируемое направление угол 30
- Примечание 0 означает все отверстия 30
- Установка пульта 30
- Фиксация 30
- Электрические работы 30
- Выполнение испытания 31
- Перед пробным прогоном 31
- Электрические работы 31
- Fig 7 1 32
- Fig 7 2 32
- Fig 7 3 32
- Fig 7 4 32
- Выполнение испытания 32
- Использование sw4 в наружном блоке 32
- Самодиагностика 32
- Выполнение испытания 33
- Fig 7 5 34
- Выполнение испытания 34
- До завершения электрических работ 34
- После завершения электрических работ 34
- Проверка дренажа fig 7 5 34
- Управление системой 34
- Fig 9 1 35
- Fig 9 2 35
- Fig 9 3 35
- Fig 9 4 35
- Fig 9 5 35
- Выбор вытяжных отверстий 35
- Подготовка fig 9 5 35
- Подготовка к установке вентиляционной решет ки fig 9 2 35
- Проверка содержимого комплекта fig 9 1 35
- Удаление воздухозаборной решетки fig 9 3 35
- Удаление угловой панели fig 9 4 35
- Установка вентиляционной решетки 35
- Fig 9 10 36
- Fig 9 6 36
- Fig 9 7 36
- Fig 9 8 36
- Fig 9 9 36
- Временная установка вентиляционной решетки fig 9 6 36
- Крепление вентиляционной решетки fig 9 7 36
- Примечание не оставляйте излишек проволочного вывода в электрической ответвительной коробке прибора 36
- Соединение проводов fig 9 8 36
- Установка вентиляционной решетки 36
- Установка воздухозаборной решетки fig 9 9 36
- Установка угловой панели i see sensor fig 9 10 36
- Fig 9 11 37
- Блокировка направления воздушного потока вверх вниз fig 9 11 37
- Проверка 37
- Установка вентиляционной решетки 37
- Функция простого техобслуживания 37
Похожие устройства
- Mitsubishi Electric PLA-RP60BA / SUZ-KA60VA Руководство по установке
- Mitsubishi Electric PLA-RP60BA / SUZ-KA60VA Сертификат
- Mitsubishi Electric PLA-RP71BA / SUZ-KA71VA Инструкция по эксплуатации
- Mitsubishi Electric PLA-RP71BA / SUZ-KA71VA Руководство по установке
- Mitsubishi Electric PLA-RP71BA / SUZ-KA71VA Сертификат
- Mitsubishi Electric PLA-RP125BA / PUHZ-P125VHA Инструкция по эксплуатации
- Mitsubishi Electric PLA-RP125BA / PUHZ-P125VHA Руководство по установке
- Mitsubishi Electric PLA-RP125BA / PUHZ-P125VHA Сертификат
- Mitsubishi Electric PLA-RP100BA / PUHZ-P100VHA Инструкция по эксплуатации
- Mitsubishi Electric PLA-RP100BA / PUHZ-P100VHA Руководство по установке
- Mitsubishi Electric PLA-RP100BA / PUHZ-P100VHA Сертификат
- ATESY Ривьера 2-х секц. 950 мм Инструкция по эксплуатации
- Mitsubishi Electric PLA-RP140BA / PU-P140YHAR Инструкция по эксплуатации
- Mitsubishi Electric PLA-RP140BA / PU-P140YHAR Руководство по установке
- Mitsubishi Electric PLA-RP140BA / PU-P140YHAR Сертификат
- Mitsubishi Electric PLA-RP50BA / SUZ-KA50VA Инструкция по эксплуатации
- Mitsubishi Electric PLA-RP50BA / SUZ-KA50VA Руководство по установке
- Mitsubishi Electric PLA-RP50BA / SUZ-KA50VA Сертификат
- Mitsubishi Electric PLA-RP125BA / PU-P125YHAR Инструкция по эксплуатации
- Mitsubishi Electric PLA-RP125BA / PU-P125YHAR Руководство по установке