9-3. Twinning kit selection
9-3-1. Indoor unit twinning kit
Select a proper indoor unit twinning kit (sold separately) based on the total capacity of the downstream indoor units,
using the table below as a reference.
Line branching
Total capacity of downstream indoor units Kit model
200 or below CMY-Y102SS-G2
201 to 400 CMY-Y102LS-G2
401 to 650 CMY-Y202S-G2
651 or above CMY-Y302S-G2
Line branching for the 1st branching point
Outdoor unit model Kit model
P450 to P650 CMY-Y202S-G2
P700 to P1350 CMY-Y302S-G2
Header branching
Total capacity of downstream indoor units Number of branches Kit model
200 or below 4 CMY-Y104-G
400 or below 8 CMY-Y108-G
650 or below 10 CMY-Y1010-G
* Use an adapter, if necessary, to connect a refrigerant pipe to a twinning pipe of a different diameter.
9-3-2. Outdoor unit twinning kit
Select a proper outdoor unit twinning kit (sold separately) based on the total capacity of the outdoor units, using the
table below as a reference.
Total capacity of outdoor units Kit model
P400 to P650 CMY-Y100VBK3
P700 to P900 CMY-Y200VBK2
P950 to P1350 CMY-Y300VBK3
9-4. Pipe connection example
Example of pipe connection between outdoor units
On-site piping
Twinning Kit
The pipe section before the twinning pipe must
have at least 500 mm (19-11/16 in) of straight
section.