Toshiba MMU-AP0184MH-E [49/219] Function code no dn code table includes all functions needed to perform applied control on site

Toshiba MMC-AP0244H-E [49/219] Function code no dn code table includes all functions needed to perform applied control on site
48
Function CODE No. (DN Code) table (includes all functions needed to perform applied control on site)
DN Item Description At shipment
01
Filter display delay timer 0000: None
0002: 2500H
0004: 10000H
0001: 150H
0003: 5000H
According to type
02
Dirty state of filter 0000: Standard
0001: High degree of dirt (Half of standard time)
0000: Standard
03
Central control address 0001: No.1 unit
0099: Unfixed
to 0064: No.64 unit 0099: Unfixed
04
Specific indoor unit
priority
0000: No priority 0001: Priority 0000: No priority
06
Heating temp shift 0000: No shift
0002: +2 °C to
0001: +1 °C
0010: +10 °C
(Up to +6 recommended)
0002: +2 °C
(Floor type 0000: 0 °C)
0d
Existence of [AUTO]
mode
0000: Provided
0001: Not provided (Automatic selection from connected outdoor unit)
0001: Not provided
0F
Cooling only 0000: Heat pump
0001: Cooling only (No display of [AUTO] [HEAT])
0000: Heat pump
10
Type 0001: 4-way Cassette etc.
* refer to 50 page Type CODE No. [10]
Depending on model
type
11
Indoor unit capacity 0000: Unfixed 0001 to 0034 According to capacity
type
12 Line address 0001: No.1 unit to 0030: No.30 unit 0099: Unfixed
13 Indoor unit address 0001: No.1 unit to 0064: No.64 unit 0099: Unfixed
14
Group address 0000: Individual
0002: Follower unit of group
0001: Header unit of group 0099: Unfixed
19
Louver type
(Air direction
adjustment)
0000: No louver 0001: Swing only According to type
0002: (1-way Cassette type, Ceiling type)
0003: (2-way Cassette type)
0004: (4-way Cassette type)
1E
Temp difference of
[AUTO] mode selection
COOL HEAT,
HEAT COOL
0000: 0 deg to 0010: 10 deg 0003: 3 deg
(Ts±1.5)
(For setup temperature, reversal of COOL / HEAT by ± (Data value) / 2)
28
Automatic restart of
power failure
0000: None 0001: Restart 0000: None
2A
Selection of option / error
input (CN70)
0000: Filter input
0002: None
0001: Alarm input (Air washer, etc.) 0002: None
2E
HA terminal (CN61)
select
0000: Usual
0002: Fire alarm input
0001: Leaving-ON prevention control 0000: Usual
(HA terminal)
31 Ventilating fan control 0000: Unavailable 0001: Available 0000: Unavailable
32 TA sensor selection 0000: Body TA sensor 0001: Remote controller sensor 0000: Body TA sensor
33 Temperature unit select 0000: °C (at factory shipment) 0001: °F 0000: °C

Содержание

Скачать